INSTRUCTION MANUAL 

BExCP3B-PB, BExCP3D-PB & BExCP3E-PB Push Button Manual Call Point 

For use in Flammable Gas and Dust Atmospheres 

 

BExCP3B-PB, BExCP3D-PB & 
BExCP3E-PB 
Manual Call Point – Push Button 
With resistor Modules 

For use in Flammable Gas and 
Combustible Dust Atmospheres 

 

1) 

Introduction 

The BExCP3B-PB/ BExCP3D-PB/ BExCP3E-PB is 
a push button manual call point which is certified to 
the  European  and  International  Gas  and  Dust 
standards. The unit meets the requirements of the 
ATEX directive 2014/34/EU and IECEx scheme. 
 
The  call  point  can  be  used  in  hazardous  areas 
where  potentially  flammable  gas  and  dust 
atmospheres may be present. 
 
All units have up to two of the following series and/ 
or EOL devices: 

 

Monitoring resistors per module: - 

 

BExCP3B-PB - 2.0W Max 

 

BExCP3D-PB - 1.0W Max  

 

BExCP3E-PB - 1.75W Max  

 

Monitoring diode 

 

Monitoring Zener diode 

 
The units are Group II, EPL (equipment protection 
level) Gb. The equipment is certified ‘Ex db eb mb 
IIC  T4  Gb’  and  as  such  may  be  used  in  Zones  1 
and 2 with flammable gases and vapours with gas 

groups  IIA,  IIB  &  IIC  and  temperature  classes  T1, 
T2, T3 and T4. 
 
These  units  are  also  Group  III,  EPL  Db.  The 
equipment is certified 
‘Ex tb IIIC T60ºC Db’ (BExCP3B-PB), 
‘Ex tb IIIC T80ºC Db’ (BExCP3D-PB), 
‘Ex tb IIIC T75ºC Db’ (BExCP3E-PB) 
and  as

 

such may  be  used in  Zones  21 and 22 for 

combustible dusts groups IIIA, IIIB & IIIC. 
 

2) 

Ratings & Marking 

All  units  have  a  rating  label,  which  carries  the 
following important information: - 
 
Unit Type No.: 
BExCP3B-PB Manual Call Point  
BExCP3D-PB Manual Call Point 
BExCP3E-PB Manual Call Point 
 
Input Voltages: 
48VDC nominal   56VDC Max   0.75A Max 
24VDC nominal   28VDC Max   5.0A Max Resistive 
Load; 3.0A Inductive Load 
12VDC nominal   15VDC Max   5.0A Max 
  6VDC nominal     9VDC Max   5.0A Max 
 
Code: 
BExCP3B-PB 

      

Ex db eb mb IIC T4 Gb      
Ex tb IIIC T60ºC Db 

      

IP66 

 

      

–40ºC <= Ta <= +50ºC      
 
BExCP3D-PB 

     

Ex db eb mb IIC T4 Gb  

     

Ex tb IIIC T80ºC Db 

 

IP66 

 

     

–40ºC <= Ta <= +70ºC      
 
Certificate No.: 
SIRA 09ATEX3286X 
IECEx SIR 09.0121X 
CSAE 21UKEX3556X 
 
Epsilon x:                           II 2GD 
 
CE Marking 
Notified  

  

2813 

Body No.               
 
UKCA Marking 
Notified Body No.

 

0518 

 
 

Year/Serial No. i.e. 20/1CP3BPB000001 

Or 

  20/1CP3DPB000001 

Or 

  20/1CP3EPB000001 

 
WARNING - DO NOT OPEN WHEN AN 
EXPLOSIVE ATMOSPHERE MAY BE PRESENT 

 
3) 

Type Approval Standards 

The  beacon  has  an  EC  Type  examination 
certificate issued by SIRA and have been approved 
to the following standards: - 
 
EN60079-0:2018 / IEC60079-0:2017 
EN60079-1:2014 / IEC60079-1:2014 
EN60079-7:2015 / IEC60079-7:2017 
EN60079-18:2015 / IEC60079-18:2014 
EN60079-31:2014 / IEC60079-31:2013 
 
The equipment is certified for use in ambient 
temperatures in the range  
BExCP3B-BG -40

o

C to +50

o

BExCP3D-BG -40

o

C to +70

o

BExCP3C-BG -40

o

C to +65

o

C  

and shall not be used outside this range. 
 

4) 

Installation Requirements 

Installation  of  this  equipment  shall  only  be  carried 
out  by  suitably  trained  personnel  in  accordance 
with the applicable code of practice e.g.  
IEC 60079-14/EN 60079-14 

 

Repair of this equipment shall only be carried out 
by the manufacturer or in accordance with the 
applicable code of practice e.g. IEC 60079-19/EN 
60079-19. 
 
Refer  to  certificates  SIRA  09ATEX3286X,  IECEx 
SIR  09.0121X  and  CSAE  21UKEX3556X  for 
special conditions of safe use. 
 
The  certification  of  this  equipment  relies  on  the 
following materials used in its construction: 
 
Enclosure:

 

Aluminium  Pressure  Die  Cast  Body 

LM6 
 
Through enclosure mechanism: Plastic Nylon Zytel 
Injection Moulded 
 
Sealing  of  enclosure  and  mechanism:  O-ring 
Acrylonitrile-Butadiene Rubber  
 
Potting Compound of resistors where used: Epoxy 
Resin 
 

If the equipment is likely to come into contact with 
aggressive substances,  then it is the  responsibility 
of the user to take suitable precautions that prevent 
it from being adversely affected, thus ensuring that 
the type of protection is not compromised. 
 
 
“Aggressive  substances”  -  e.g.  acidic  liquids  or 
gases that may attack metals, or solvents that may 
affect polymeric materials. 
 
“Suitable precautions” - e.g. regular checks as part 
of  routine  inspections  or  establishing  from  the 
material’s  data  sheet  that  it  is  resistant  to  specific 
chemicals. 
 

5) 

Call Point Location and Mounting 

The location of the call point should enable ease of 
access  for  operation  and  testing.  The  unit  should 
be  mounted  using  the  4  off  fixing  holes  which  will 
accept up to M4 sized fixings. 
 

 

View of base unit showing fixing centres. 
 
To  gain  access  to  the  mounting  holes  in  the  base 
the front cover must be removed.  
This is achieved by removing the 4 off M4 cap 
head bolts holding on the cover.

BExCP3E-PB 

     

Ex db eb mb IIC T4 Gb  
Ex tb IIIC T75ºC Db 

 

IP66 

 

     

–40ºC <= Ta <= +65ºC      

 

Summary of Contents for BExCP3D-PB

Page 1: ...P3BPB000001 Or 20 1CP3DPB000001 Or 20 1CP3EPB000001 WARNING DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE MAY BE PRESENT 3 Type Approval Standards The beacon has an EC Type examination certificate issued b...

Page 2: ...to 4 0mm For the 8 way DIN rail wire sizes allowable are 0 5mm to 2 5mm Leads connected to the terminals shall be insulated for the appropriate voltage and this insulation shall extend to within 1mm...

Page 3: ...re fault tolerance of 0 at SIL 2 The product was assessed against failure modes Failure to close a contact when the call point is struck with specified force Failure to open a contact when the call po...

Page 4: ...perated condition Unoperated condition Glass Intact Standby Condition Terminals 2 3 4 5 open Terminals 2 3 6 closed Operated condition Glass Broken Button pushed in Terminals 2 3 4 5 closed Terminals...

Page 5: ...nds B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment BExCP3A BExCP3B BExCP3C BExCP3D BExCP3E II 2G Ex db...

Page 6: ...y high concern Other Standards and Regulations EN 60529 1992 A2 2013 Degrees of protection provided by enclosures IP code enclosure rated IP66 Construction and design requirements according to EN54 11...

Page 7: ...CP3A BExCP3B BExCP3C BExCP3D BExCP3E II 2G Ex db eb IIC T6 Gb 40 C Ta 70 C II 2D Ex tb IIIC T75 C Db 40 C Ta 70 C or II 2G Ex db eb mb IIC T4 Gb 40 C Ta 50 C II 2D Ex tb IIIC T60 C Db 40 C Ta 50 C or...

Page 8: ...d by enclosures IP code enclosure rated IP66 Construction and design requirements according to EN54 11 2001 clause 4 7 BExCP3A BG B BG C BG D BG only fitted with burning house symbol shown in figure 3...

Reviews: