Document No. IS 2446-76-P Issue 1 25/02/13 Sheet 5 of 6
Mod No: ACN0012
TONE SELECTION TABLE
Note Switch No. 6 is not used
16)
CAUTION! - Ensure correct orientation of
Beacon Housing onto Sounder housing when
closing unit
Please note that due to the tight spacing internally the
Beacon housing can only be closed in one orientation relative
to the Sounder housing, otherwise PCB boards may become
damaged.
The M20 entries on the Beacon housing must be aligned with
the product labels on the side of the Sounder housing (both
M20 entries and labels on the same side).
Tone Selection
DIP Switch
Settings
Stage 1
Frequency Description
1 2 3 4 5
1
Continuous 1000Hz
Toxic gas alarm
0 0 0 0 0
2
Alternating
800/1000Hz
at
0.25s
intervals
1 0 0 0 0
3
Slow Whoop 500/1200Hz at 0.3Hz
with 0.5s gap repeated
0 1 0 0 0
4
Sweeping 800/1000 at 1Hz
1 1 0 0 0
5
Continuous at 2400Hz
0 0 1 0 0
6
Sweeping 2400/2900Hz at 7Hz
1 0 1 0 0
7
Sweeping 2400/2900Hz at 1Hz
0 1 1 0 0
8
Siren 500/1200/500Hz at 0.3Hz
1 1 1 0 0
9
Sawtooth 1200/500Hz at 1Hz
0 0 0 1 0
10
Alternating 2400/2900Hz at 2Hz
1 0 0 1 0
11
Intermittent 1000Hz at 0.5Hz
General
alarm
0 1 0 1 0
12
Alternating 800/1000Hz at 0.875Hz
1 1 0 1 0
13
Intermittent 2400Hz at 1Hz
0 0 1 1 0
14
Intermittent 800Hz 0.25s on 1s off
1 0 1 1 0
15
Continuous at 800Hz
0 1 1 1 0
16
Intermittent 660Hz 150mS on, 150mS
off
1 1 1 1 0
17
Alternating 544Hz
(100mS)/440Hz(400mS)
0 0 0 0 1
18
Intermittent 660Hz 1.8s on, 1.8s off
1 0 0 0 1
19
1400Hz to 1600Hz sweep up over 1s -
1600Hz to 1400Hz sweep down over
0.5s
0 1 0 0 1
20
Continuous 660Hz
1 1 0 0 1
21
Alternating 554/440Hz at 1Hz
0 0 1 0 1
22
Intermittent 554Hz at 0.875Hz
1 0 1 0 1
23
800Hz pulsing at 2Hz
0 1 1 0 1
24
Sweeping 800/1000Hz at 50Hz
1 1 1 0 1
25
Sweeping 2400/2900Hz at 50Hz
0 0 0 1 1
26
Simulated bell sound
1 0 0 1 1
27
Continuous 554Hz
0 1 0 1 1
28
Continuous 440Hz
1 1 0 1 1
29
Sweeping 800/1000Hz at 7Hz
0 0 1 1 1
30
420Hz repeating 0.625s on, 0.625s off
Australian alert signal
1 0 1 1 1
31
1200/500Hz at 1 Hz
Prepare to abandon platform
0 1 1 1 1
32
Sweeping 500/1200Hz 3.75s on, 0.25s
off 15Hz
1 1 1 1 1
Customer Connection
Power Supply Wires
-ve to Beacon, +ve to
Telephone PCB
BExDCTS110-05D DC Wiring Diagram
BExDCTS110-05D AC Wiring Diagram
Sounder &
Telephone
Section
Beacon Section
Sounder &
Telephone
Section
Customer Connection
Power Supply Wires
N to Beacon, L to
Telephone PCB
Figure 8
Figure 9
Beacon Section