E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com e2s.com D172
-
00
-
001
-
IS Issue 1 14/05/2021
•
All models are approved for use as Audible Signal Appliance
for use as General Signaling: UL464A & CSA C22.2 No 205
-
17
•
Type 4 / 4X / 3R / 13, IP66
•
-
40°C to +66°C /
-
40°C to +151°F
General Signaling Canada:
D105DC024:
-
40°C to +55°C /
-
40°F to +131°F
D105AC230:
-
40°C to +40°C /
-
40°F to +104°F
•
To maintain Ingress Protection, cable entries must be fitted with suitably rated cable glands or stopping plugs
•
EOL Monitoring (DC Only): End of Line Devices may be fitted between the +ve &
-
ve terminals of the PCBA. Please ensure that the device
legs meet the wire size range stated for the connection terminals and are fitted correctly in order to avoid a short. Refer to the compatible
control panel specification for EOL device values and ratings.
Model
Nominal Voltage
Voltage Range
Nominal Operating Current
#
Max Operating RMS*
D105DC024
12V dc
10
-
60V ac
17mA
125mA
24V dc
33.5mA
48V dc
113mA
24
-
260V ac 50/60Hz /
60
-
260V dc
42.5mA
D105DAC230
48V ac
42mA
115V ac
25mA
230V ac
17mA
*Max Operating current for worst
-
case input voltage;
#
Nominal current at nominal voltage and Tone 12