E2S Warning Signals 

Impress House, Mansell Road, Acton, London W3 7QH    sales@e2s.com         e2s.com

 

       D172

-

00

-

001

-

IS

-

UL Issue A  19/04/2021

 

 

FIRE INSTRUCTION & SERVICE MANUAL

 

D105 Range AlertAlarm Sounder UL464 / CAN/ULC

-

S525

 

Model: D105DC

 

 

 

Surge Current Ratings for use in fire alarm systems

 

Model

 

Nominal Voltage

 

Voltage Range

 

Initial Peak

 

Initial RMS

 

D105DC024 

 

24V dc 

 

10 

-

 60V dc 

 

298mA

 

56.4mA 

 

D105DC024 Sounder Directional Characteristics for Canadian Fire CAN/ULC

-

S525 at 10 feet

 

Horizontal Axis

 

Vertical Axis

 

Angle

 

OSPL

 

Angle

 

OSPL

 

Angle

 

OSPL

 

Angle

 

OSPL

 

Ref. 90°

 

98.2 dB(A)

 

Ref. 90°

 

98.2 dB(A)

 

Ref.90°

 

98.3 dB(A)

 

Ref. 90°

 

98.3 dB(A)

 

112°

 

-

3 dB(A)

 

65.5°

 

-

3 dB(A)

 

113°

 

-

3 dB(A)

 

66°

 

-

3 dB(A)

 

149°

 

-

6 dB(A)

 

30°

 

-

6 dB(A)

 

148°

 

-

6 dB(A)

 

30°

 

-

6 dB(A)

 

180°

 

84.3dB(A)

 

 

83.6 dB(A)

 

180°

 

84.2 dB(A)

 

 

84.2 dB(A)

 

Attention: Installation must be carried out by an electrician in compliance with the National Electrical Code, NFPA 70, and the National Fire Alarm 
Signaling Code, NFPA 72 or CSA 22.1 Canadian Electrical Code, Part I, Safety Standard for Electrical Installations, Section 32. /  L'installation doit 
exclusivement être réalisée par du personnel qualifié, conformément au code national d'électricité américain, NFPA 70, et le code national d

alarrme 

incendie et de signalisation NFPA 72 ou CSA 22.1 Code canadien de l'électricité, première partie, norme de sécurité relative aux installations électriques, 
Section 32

 

Attention: Disconnect from power source before installation or service to prevent electric shock / Débranchez

-

le de la source d'alimentation avant l'instal-

lation ou l'entretien pour éviter tout choc électrique.

 

Attention: Do not paint / Ne pas Peinturer

 

• 

-

40°C to +66°C / 

-

40°F to +151°F

 

• 

Units can be mounted using the 2

-

off 10 x 7mm obround holes in the mounting lugs.

 

• 

D105DC024 is approved for use as an audible signal appliance for fire alarm use –

 

Public Mode (UL464 & CAN/ULC

-

S525) and produc-

es a minimum sound pressure level of US: 78.96dB(A); CA: 88.8dB(A) at 10 feet, (figures @ worst case 10Vdc).

 

• 

@24Vdc the D105DC024 produces a minimum sound pressure level of US: 87.39dB(A) ; CA: 97.1dB(A)  at 10 feet

 

• 

For Fire Alarm applications, the Sounder Volume must be at the highest setting, (see volume control section). For fire alarm use, Tone 

12 as shown below must be selected:

 

 

 

 

 

 

 

 

 

• 

Connection Terminals: Pluggable

 

 

 

AC: 1.0 

-

 2.5mm

2

 / AWG18 

-

 AWG12

 

                                  DC: 0.2 

-

 2.5mm

2

 / AWG24 

-

 AWG12

 

• 

Terminal Tightening torque 0.4Nm

 

• 

To maintain Ingress Protection, cable entries must be fitted with suitably rated cable glands or stopping plugs

 

• 

Units can be located indoor or outdoor wet use, wall or ceiling mounted and there are no limitations on orientation

 

• 

Factory finishes are not intended to be modified

 

+ +   

-

  

-

  S2 S3

 

S2       S1

 

1000Hz(0.5s on, 0.5s off)x3 + 1s gap ISO 8201 Temporal 
Pattern

Stage 1
Set DIP
SW 1
Tone No.

Tone Description

Tone Visual

Stage 1 & 2
DIP SW 1/2

 Settings

1 2 3 4 5 6

Stage 3
Set DIP

SW 1

(S3)

Stage 4
Set DIP

SW 1

(S2 + S3)

12

1 1 0 1 0 0

1000Hz 0.5s

0.5s

0.5s

0.5s

0.5s

1s

1

8

Summary of Contents for D105 AlertAlarm

Page 1: ...is recentes Внимание установка должна выполняться электриком в соответствии с последними нормами и правилами Attention Disconnect from power source before installation or service to prevent electric shock Attention Débranchez le de la source d alimentation avant l installation ou l entretien pour éviter tout choc électrique Achtung Vor Installation oder Wartung von der Stromquelle trennen um einen...

Page 2: ...use Mansell Road Acton London W3 7QH sales e2s com e2s com D172 00 001 IS Issue 1 14 05 2021 S2 S3 S2 S1 S2 S1 E E S3 S2 N L Default S2 Tone 1 Default S1 Tone 44 ON 1 OFF 0 AC DC See D221 95 001 DC AC See D218 06 001 See D218 06 005 ...

Page 3: ...e2s com D172 00 001 IS Issue 1 14 05 2021 4x 1Nm For D105AC units wire an Earth to the E terminal on the PCBA in order to Earth the metal housing For D105DC units using a ring terminal fit an Earth to the shown location underneath the M4 screw and M4 spring washer This point shall not be used for any other purpose e g ground bonding ...

Page 4: ...s or stopping plugs EOL Monitoring DC Only End of Line Devices may be fitted between the ve ve terminals of the PCBA Please ensure that the device legs meet the wire size range stated for the connection terminals and are fitted correctly in order to avoid a short Refer to the compatible control panel specification for EOL device values and ratings Model Nominal Voltage Voltage Range Nominal Operat...

Page 5: ...iques Section 32 Attention Disconnect from power source before installation or service to prevent electric shock Débranchez le de la source d alimentation avant l instal lation ou l entretien pour éviter tout choc électrique Attention Do not paint Ne pas Peinturer 40 C to 66 C 40 F to 151 F Units can be mounted using the 2 off 10 x 7mm obround holes in the mounting lugs D105DC024 is approved for u...

Page 6: ...A105N D105 DC SOUNDER WIRING DIAGRAMS INTRODUCTION NTS 1 1 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120Ω MIN 2W MIN OR 1KΩ MIN 0 5W MIN 28V MAX SYSTEM 470Ω MIN 2W MIN OR 2 4KΩ MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Single Stage Configuration Config 1a Line Monitoring Stage 1 Apply Power to Stage 1 ve Stage 1 ve Two Stage Configuration Config 1b Common Positive Stage 1...

Page 7: ...LE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D218 06 005 R S RAIT B ISARD R N POTTS OF A100 A105N D105 AC WIRING DIAGRAMS NTS 1 SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED 1 Single Stage Configuration Config 1a Stage 1 Apply Power to Stage 1 Live Stage 1 Neutral Three Four Stage Configuration Config 1b Stage 1 Apply Powe...

Page 8: ... 0 0 0 1 0 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 0 0 0 0 1 0 0 1 0 0 1 0 0 0 1 0 1 0 0 1 1 0 1 0 0 0 0 1 1 0 0 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 0 0 1 0 0 1 0 1 1 0 0 1 0 0 0 1 0 1 0 1 0 1 0 1 0 0 1 1 0 1 0 1 1 1 0 1 0 1 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 1 1 0 0 0 1 0 0 1 0 0 1 1 0 1 0 0 1 0 1 1 0 0 1 1 1 1 0 0 1 0 0 0 1 0 1 0 1 0 1 0 1 1 0 1 1 0 1 0 1 1 1 0...

Reviews: