background image

 

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D190-00-671-IS

 

Issue 2

 

06-03-2023

 

 

Sheet 3 of 15

 

 

5) 

Specific Conditions of Installation 

 

ATEx/IECEx & UKEx Installations: 
 

The cable entries have two M20 x 1.5 

 6H entry thread and a 

single  ½”  NPT  thread.  If  the  installation  is  made  using  cable 

glands, only suitably rated ATEx/IECEx or UKEx certified cable 
glands must be used. They must be suitable for the type of cable 
being  used  and  also  meet  the  requirements  of  the  current 
installation standards EN 60079-14 / IEC60079-14. 
 
If the installation is made using conduit, openings must have a 
sealing fitting connected as close as practical to the wall of the 
enclosure, but in no case more than the size of the conduit or 
50mm, whichever is the lesser. 
 
Any unused cable entries must be closed with suitably rated and 
UKEx certified blanking plugs. 
 

For high ambient temperatures the cable entry temperature 

may exceed 70ºC or the cable branching point temperature 

may  exceed  80ºC  and  therefore  suitable  heat  resisting 

cables and cable glands must be used, with a rated service 

temperature at least as stated below:

 

 

NEC / CEC Installations: 
 

The cable entries have two M20 x 1.5 

 6H entry thread and a 

single  ½”  NPT  thread.  If  the  installation  is  made  using  cable 

glands, only suitably rated and UKEx certified cable glands must 
be used. They must be suitable for the type of cable being used 
and  also  meet  the  requirements  of  the  current  installation 
standards for NEC & CEC. 
 
If the installation is made using conduit, openings must have a 

sealing fitting connected within 18” of enclosure.

 

 
Any unused cable entries must be closed with suitably rated and 
certified blanking plugs. 
 

All Installations: 
 
The plastic horn is not anti-static and the metallic enclosure has a non-
conductive coating. These may generate an ignition-capable level of 
electrostatic  charges  under  certain  extreme  conditions.  The  user 
should ensure that the equipment is not installed in a location where it 
may be subjected to external conditions that might cause a build-up of 
electrostatic charges on non-conducting surfaces. 
 

Only  the  explosionproof  cover  is  to  be  used  for  access  to  the 

enclosure for installation, service and maintenance.

 

 

6) 

Specific Conditions for Safe Use 

 

Flameproof threaded joints and cemented joints are not permitted to 
be repaired. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

7) 

Product Mounting and Access 

 

7.1.  Mounting 

 

The D1x Alarm Horn may be secured to any flat surface using at 

least  two  of  the  three  or  four  7mm  fixing  holes.  The  enclosure 

provides IP66 protection and is suitable for installation in exterior 

locations providing it is positioned so that water cannot collect in 

the horn, and the cable entry is sealed.

 

 

14

 5

.7

in

30

  1

.1

in

30

  1

.1

in

236.9  9.33 in. 

21

9.

 8

.6

in

335.9  13.23 in. 

314.5  12.38 in. 

40

3.

 1

5.

87

 in

465.9  18.34 in. 

55  2.17 in. 

59

  2

.3

in

59

  2

.3

in

21

 8

.4

in

 

 

Fig 1: Mounting Locations 

 

The Equipment must not be installed with the horn facing upwards 

of horizontal.

 

 

 
 
 
 

 

  

7.2.  Installation procedure 

  

a. 

Secure  the  D1x  unit  to  a  flat  surface  via the  three  7mm 
fixing holes in the mounting    bracket.  

b.

  

Remove  the  explosionproof  cover  of  the  alarm  horn  by 
unscrewing  it,  taking  care  not  to  damage  the 
explosionproof  threads  in  the  process  (Refer  to  section 
7.4).  

c.

  

Fit an M20/NPT suitably rated cable gland or conduit entry 
into the hole in the enclosure and connect the field wiring 
to the appropriate alarm horn terminals as shown in D190-
06-651. The power supply terminals are duplicated so that 
units  may  be  connected  in  parallel.  An  end  of  line 
monitoring  resistor  may  be  fitted  to  DC  units  only  (see 
section 10). If the second and third M20/NPT entries are 
not  used,  suitably  rated  stopping  plugs  must  always  be 
fitted. 

d.

  

Replace  the  explosionproof  cover  of  the  loudspeaker, 
taking  care  not  to  damage  the  explosionproof  threads. 
Tighten fully. 

  

7.3.  Hornless Variants 

  

The D1x Sounder is also available as a variant with no horn fitted 

in  the  factory.  The  Horn  threaded  nose  portion  has  a  fitment 

thread  of  1-3/8”  –  18  UNF  (to  BS1580  or  ANSI  B1.1).  The 

customer is responsible for sourcing and correctly fitting a suitable 

horn that meets all of the relevant safety requirements.

 

 
 
 
 
 
 
 
 
 
 
 

Minimum Ratings of Cables & Cable Glands

 

Max Ambient Temp (°C) 

55 

60 

65 

70 

75 

D1xS2FDC024-S/D1xS2HDC024-S  
Min. Rating (°C) 

70 

75 

80 

85 

90 

Table 2: Min. Ratings of Cables & Cable Glands. 

D1xS2F 

D1xS2H 

Summary of Contents for D1xS2HDC024-S

Page 1: ...WARNING FIT SEALING FITTING IN CONDUIT RUNS WITHIN 18 INCHES FROM ENCLOSURE EQUIPMENT MUST NOT BE INSTALLED WITH THE HORN FACING UPWARDS OF HORIZONTAL DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT DO NOT OPEN WHEN ENERGISED POTENTIAL ELECTROSTATIC CHARGING HAZARD CLEAN ONLY WITH A DAMP CLOTH ENCLOSURE ENTRIES TWIN M20 X 1 5 SINGLE 1 2 NPT ATEX IECEx UKEx INSTALLATIONS IF TEMPERATURE EXCEEDS ...

Page 2: ... IIC T6 Gb Ta 55 C to 60 C Ex tb IIIC T95 C Db Ta 55 C to 75 C See Product table for electrical ratings of each unit model Certificate No DEMKO 19ATEX2141X IECEx ULD 19 0008X UKEx UL UL21UKEX2132X Epsilon x Equipment Group and Category II 2G II 2D CE Marking and Notified Body No 2813 UKCA Marking and Notified Body No 0518 4 Zones Gas Group Category and Temperature Classification The units can be i...

Page 3: ...ld up of electrostatic charges on non conducting surfaces Only the explosionproof cover is to be used for access to the enclosure for installation service and maintenance 6 Specific Conditions for Safe Use Flameproof threaded joints and cemented joints are not permitted to be repaired 7 Product Mounting and Access 7 1 Mounting The D1x Alarm Horn may be secured to any flat surface using at least tw...

Page 4: ... on the line and the length of the cable runs The cable size selected must have the necessary capacity to provide the input current to all the sounders connected to the line DC 0 2 2 5mm2 AWG24 AWG12 Fig 3 Wire Preparation When connecting wires to the terminals great care should be taken to dress the wires so that when the cover is inserted into the chamber the wires do not exert excess pressure o...

Page 5: ...switching Fig 6 Stage Switching Polarity 9 3 Tone Selection The D1x Alarm Horn Sounders have 64 different tones that can be selected independently for the first and second stage alarms The tones are selected by operation of the tone setting DIP switch 1 DIP switch 2 see fig 7 on the PCB for stage 1 and stage 2 respectively Default Switch 2 S2 Tone 1 0 0 0 0 0 0 Default Switch 1 S1 Tone 44 1 1 0 1 ...

Page 6: ... 0 5W or a minimum resistance value of 500 ohms and a minimum wattage of 2W The resistor must be connected directly across the ve and ve terminals as shown in the following drawing The resistor leads should be kept as short as possible SIL2 line monitoring module product version see section 20 for standard default values and product coding See document D190 06 651 for associated wiring diagram Fig...

Page 7: ... End of Line Devices may be fitted between the ve ve terminals of the PCBA Please ensure that the device legs meet the wire size range stated for the connection terminals and are fitted correctly in order to avoid a short Refer to the compatible control panel specification for EOL device values and ratings Model Nominal Voltage Voltage Range P1 Nominal Operating Current P2 Nominal Operating Curren...

Page 8: ...operates as part of a SIL 2 system The sounder will after commissioning remain powered in Standby mode reverse polarity until the sounder is required to operate When the signaling device is required to operate the polarity is changed to normal supply and the sounder will go into Active mode where it will start to sound the correct tone When periodically testing the system and sounders operation is...

Page 9: ...arity mode When Commissioning system the power must not be disrupted to the SIL 2 Unit within the unit s initialization cycle which is 5 seconds Once past this period the SIL 2 system is fully operational and will be in monitoring the sounder and power in Standby mode The relay RLY1 2 on the SIL 2 unit will only remain open for a maximum of 1 second on commissioning start up RLY1 2 will subsequent...

Page 10: ...ounder check on pattern generation and signal output checks Important Only tones use tones that are stated as SIL 2 approved for the SIL 2 application Ensure that the unit is set to one of these tones see in Tone Table D221 95 651 IS As factory default the sounder should be set to Stage 1 Dip SW1 to Tone 44 and Stage 2 Dip SW2 to Tone 1 J3 Header Hard Reset Shown in factory default position A see ...

Page 11: ...rom the circuit Note a cable short circuit will not be detectable in this configuration For one unit only Sounder power supply terminal block Current drawn mA Active Mode 190mA Standby Mode 25mA SIL2 TB1 Current Sense Resistor value Current drawn mA 3 3kΩ 7 2mA On fault mode current drops to 0 as circuit goes open Figure 11 Schematic of SIL 2 system wiring for fault detection in standby and active...

Page 12: ... SIL 2 alarm horn sounders are to be cabled in series the monitoring connections differ from that of a single alarm horn sounder For more information see manual D197 00 651 IS available from the E2S website I Total Current drawn IFR Current drawn from Fault Resistor IEOL Current drawn from Customer EOL resistor ISIL Current drawn from SIL board INF Standby Mode Total Current drawn No Fault IFR 0mA...

Page 13: ...tion B pins 2 3 linked Places power supply terminal Fault resistor RLY 1 2 in circuit As used in 2 Wire Configuration Figure 14 J2 Header pin positions Fault Resistor FR 16 4 SIL 2 Hard Reset Function Power down the unit completely for a minimum of 30 seconds Move the hard reset header pin Jumper J3 to reset position B shown Then power the unit for a minimum of 5 seconds Power down the unit for 30...

Page 14: ...no input D1xS2FDC024 S D1xS2HDC024 S Failure to Sound Integrity in respect of failure to release SIL 2 Total Failure rate 0 447 pmh hazardous failure rate revealed 0 443 pmh hazardous failure rate unrevealed 0 004 pmh safe failure rate revealed 0 002 pmh safe failure rate unrevealed 0 Diagnostic Coverage 99 System type B Hardware Fault Tolerance 0 Safe Failure Fraction 99 PFD hazardous failure 3 3...

Page 15: ...values of resistors available are shown in table 7 below Code Resistor Value Default resistor coding as follows D1xS2FDC024AB1S1R AFZ Example of a custom requirement resistor coding D1xS2FDC024AB1S1R GEF Where the FR Fault Resistor is G 3 9 kΩ CSR Current Sense Resistor is E 2 7 kΩ EOL End Of Line resistor is F 3 3 kΩ A 2 2 kΩ B 1 0 kΩ C 1 5 kΩ D 1 8 kΩ E 2 7 kΩ F 3 3 kΩ G 3 9 kΩ H 4 7 kΩ J 5 6 kΩ...

Page 16: ... 0 1 0 0 1 0 1 1 0 0 1 0 0 0 1 0 1 0 1 0 1 0 1 0 0 1 1 0 1 0 1 1 1 0 1 0 1 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 1 1 0 0 0 1 0 0 1 0 0 1 1 0 1 0 0 1 0 1 1 0 0 1 1 1 1 0 0 1 0 0 0 1 0 1 0 1 0 1 0 1 1 0 1 1 0 1 0 1 1 1 0 1 1 1 1 1 0 1 0 0 0 0 1 1 1 0 0 0 1 1 0 1 0 0 1 1 1 1 0 0 1 1 0 0 1 0 1 1 1 0 1 0 1 1 0 1 1 0 1 1 1 1 1 0 1 1 0 0 0 1 1 1 1 0 0 1 1 1 0 1 0 1 1 1 1 1 0 1 1 1 0 0...

Page 17: ...ve OUT Common ve IN Common ve OUT Stage 2 ve Stage 1 ve IN Stage 1 ve OUT Common ve IN Common ve OUT Stage 2 ve Stage 3 ve EOL EOL S2 EOL S2 S3 Stage 1 ve IN Stage 1 ve OUT Stage 1 ve IN Stage 1 ve OUT Single Stage Configuration Config 1a Line Monitoring Set to positive switching default Stage 1 Apply Power to Stage 1 ve Stage 1 ve For full 4 Wire SIL 2 Connection Monitor SIL 2 ve and SIL 2 ve Ter...

Page 18: ...S NTS SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED Stage 2 ve Common ve IN Common ve OUT Stage 1 ve OUT Stage 3 ve Stage 1 ve IN H2 H1 OF 2 2 EOL S2 S3 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED EOL Set H1 H2 to ve switching Three Four Stages Voltage Free 2nd 3rd 4th Stage Activation Configuration Config 2 Common Positive Customer Set H1 H2 to Negative Switching See Below Stage 1 Apply ...

Page 19: ...awarden Industrial Park Hawarden Deeside CH5 3US UK Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 GB II 2D Ex tb IIIC T82 C 145 C Db Standards applied EN 60079 0 2018 EN 60079 1 2014 EN60079 31 2014 Directive 2014 30 EU Electromagnetic Compatibility Directive EMC Standards applied EN 61000 6 1 2007 EN 61000 6 2 2005 EN 61000 6...

Page 20: ...te and Place of Issue London 10 02 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives regulations and standards This Declaration is issued under the sole responsibility of the ma...

Page 21: ... CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 GB II 2D Ex tb IIIC T82 C 145 C Db Standards applied EN 60079 0 2018 EN 60079 1 2014 EN60079 31 2014 Directive 2014 30 EU Electromagnetic Compatibility Directive EMC Standards applied EN 61000 6 1 2007 EN 61000 6 2 2005 EN 61000 6 3 2007 A1 2011 AC 2012 EN 61000 6 4 2007...

Page 22: ...ate and Place of Issue London 24 02 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives regulations and standards This Declaration is issued under the sole responsibility of the...

Reviews: