background image

 

 

European Safety Systems Ltd.

  Impress House, Mansell Road, Acton, London W3 7QH 

 

 

 

 

 

 

 

www.e2s.com  Tel: +44 (0)208 743 8880 

Document D154-00-151-IS   Issue 8  12-09-2022 

 

 

Sheet 2 of 3 

 

 

 

 

 

This  is  achieved  by  removing  the  4  off  M4  cap 
head bolts holding on the cover. 
 
 
 
 
 
 

 

 

 

 

 
 
Once  the  screws  are  removed  the  cover  will  hang 
down  out  of  the  way  to  gain  access  to  the  Ex  e 
terminal  block,  the  internal  earth  terminal  and 
mounting hole recesses. 
 

6) 

Earthing 

The unit has an internal earth terminal. 
It  is  recommended  that  a  cable  crimp  lug  is  used 
on the earth wires. 
The  internal  earth  wire  is  placed  under  an  earth 
clamp  which  will  stop  the  cable  twisting.  This  is 
secured by an M4 screw and spring washer. 
 

 

 
 
 
 

 
 

 

 
Internal Earth 

Ex e terminal block 

terminal 

 

 

 

Note: Depending on options chosen an 8-Way DIN 
Rail or 6-Way terminal block may be selected. 
 

7) 

Cable connections 

There  are  3  off  cable  entries  for  M20x1.5  Ex  e 
approved  cable  glands  or  stopping  plugs  with  a 
minimum ingress protection of IP66 
 
The unit can be wired in a number of different ways 
depending on the device combination selected. 
 
EOL (End of line) device;  
resistor – ExxxR / diode – ED1 / zener – ExxxZ  
Series (In line) device;  
resistor  –  SxxxR  /  diode  –  SD1  /  zener  –  SxxxZ  / 
LED  
Microswitch 1 = M/S 1 
Microswitch 2 = M/S 2 
 
The unit can be wired with a maximum of 2 module 
devices – refer to wiring schematic D154-06-051 
 

Voltage 
option 

Max 
Voltage 

Min 
resistor 
value 
allowable 
in module 
Type B 
unit 
(2.0W) 

Min 
resistor 
value 
allowable 
in module 
Type D 
unit  
(1.0W) 

Min 
resistor 
value 
allowable 
in module 
Type E 
unit 
(1.75W) 

6 V dc 

9 V dc 

47 ohms 

91 ohms 

51 ohms 

12V dc 

15 V dc 

120 ohms 

240 ohms 

150 ohms 

24V dc 

28 V dc 

470 ohms 

820 ohms 

510 ohms 

48V dc 

56 V dc 

1K8 ohms 

3K3 ohms 

2K0 ohms 

 
When  wiring  to  Increased  Safety  terminal 
enclosures,  you are only permitted  to  connect  one 
wire  into  each  way  on  the  terminal  block  unless  a 
pair of wires are crimped into a suitable ferrule.  
For the six-way terminal block wire sizes allowable 
are 0.5mm² to 4.0mm². For the 8-way DIN rail wire 
sizes allowable are 0.5mm² to 2.5mm². 
 
Leads connected to the terminals shall be insulated 
for the appropriate voltage and this insulation shall 
extend  to  within  1mm  of  the  metal  of  the  terminal 
throat.  They  shall  only  be  installed  and  wired  with 
cable in an ambient temperature of -10°C to +80°C 
 
All  terminal  screws,  used  or  unused,  shall  be 
tightened down to between 0.5 Nm and 0.7 Nm 
 
 
 
 
 

7.1)     Fitted LED, Diode or Zener Diode 

If a diode module is pre-fitted as either an EOL or 
series  device,  the  following  current  limitation 
applies: 
 

Unit Voltage 

Max. Current 

48V DC 

0.75A  

6, 12 & 24V DC 

2.0A 

 
If a Zener diode module is pre-fitted as either EOL 
or  Series  device,  the  following  current  limitation 
applies: 
 

Zener 
Voltage 

Max. Input 
Voltage 

Max. Current 

3.3V 

56V DC 

230mA 

4.7V 

162mA 

5.1V 

149mA 

5.6V 

136mA 

6.2V 

122mA 

6.8V 

112mA 

10V 

76mA 

12V 

63mA 

 
If  an  LED  indicator  is  pre-fitted  (optional  on 
GNExCP6B  Units  only),  the  LED  is  protected  by 
the  LED  current-limiting  resistor.  See  value  of  this 
resistor  in  table  below.  This  only  applies  to  units 
with LED option code ‘L’. 
 

GNExCP6B-PBXXXXXXXXX

L

-XX-ExxxR-SxxxR  

 

LED Resistor 

Max. Input Voltage 

3K3 (3300Ω) 

56V DC 

1K5 (1500Ω) 

28V DC 

 
In  any  scenario,  the  lowest  value  of  maximum 
current should be used. For example, if the unit has 
both  a  diode  and  a  Zener  diode,  the  Zener  diode 
would determine the maximum input current of the 
unit, since its max. current is lowest. 
 

8) 

Testing unit operation 

The  push  button  unit  can  be  tested  without  the 
need to replace any element. 
 
To  test,  lift  the  cover  lift  flap  to  reveal  the  push 
button. The button should be pressed into the body 
to  activate  the  unit  and  place  it  into  the  operated 
condition. 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
The  call  point  switch  will  now  change  over  its 
contacts to operate the alarm. 
 
Once testing is complete the unit needs to be reset 
from the operated condition. 
 
Rotate  the  push  button  anticlockwise  by  an  angle 
of  55°,  see  guide  alignment  marks  on  the  button 
and  cover,  shown  below  (1).  The  push  button 
should pop back up to its original position. 
Ensure that the push button has also twisted  back 
clockwise  by  55°  to  its  original  position  see  guide 
marks  on button and cover, shown  below  (2). The 
unit is now reset 
 
 
 
 
 
 
 
 
 
 
 
 

 

1. On operated unit 

           2. Button should pop 

twist push button 

          up and twist back to 

anticlockwise 55° 

          original position 

to reset 
 

Summary of Contents for GNExCP6B-BG

Page 1: ...BE PRESENT ELECTROSTATIC HAZARD CLEAN ONLY WITH A DAMP CLOTH 3 Type Approval Standards The call point has an EC Type examination certificate issued by SIRA and have been approved to the following standards EN60079 0 2018 IEC60079 0 2017 EN60079 1 2014 IEC60079 1 2014 EN60079 7 2015 IEC60079 7 2017 EN60079 18 2015 IEC60079 18 2014 EN60079 31 2014 IEC60079 31 2013 The equipment is certified for use ...

Page 2: ...ed to the terminals shall be insulated for the appropriate voltage and this insulation shall extend to within 1mm of the metal of the terminal throat They shall only be installed and wired with cable in an ambient temperature of 10 C to 80 C All terminal screws used or unused shall be tightened down to between 0 5 Nm and 0 7 Nm 7 1 Fitted LED Diode or Zener Diode If a diode module is pre fitted as...

Page 3: ... was assessed against failure modes Failure to close a contact when the call point is struck with specified force Failure to open a contact when the call point is struck with specified force Spurious output despite no input Integrity in respect of failure to close SIL 2 Total Failure rate 0 133 pmh hazardous failure rate revealed 0 pmh hazardous failure rate unrevealed 0 1 pmh safe failure rate re...

Page 4: ...E BG GNExCP6B C D E PB GNExCP6B C D E PT DESCRIPTION GNExCP6B C D E BG BREAK GLASS MANUAL CALL POINT GNExCP6B C D E PB PUSH BUTTON MANUAL CALL POINT GNExCP6B C D E PT TOOL RESET MANUAL CALL POINT 1A Circuit shown in Unoperated condition Glass Intact Standby Condition Terminals 2 3 4 5 open Terminals 2 3 6 closed 1B Circuit shown in Operated condition Glass Broken Button pushed in Terminals 2 3 4 5...

Page 5: ... COMMUNICATED IN CONFIDENCE AND IS THE COPYRIGHT PROPERTY OF EUROPEAN SAFETY SYSTEMS LTD NEITHER THE WHOLE OR ANY EXTRACT MAY BE DISCLOSED LOANED COPIED OR USED FOR DRAWING TO BS8888 2000 GEOMETRIC TOLERANCES TO ISO1101 1983 SEE SHEET 1 D A H 28 08 2020 warning signals 5A Circuit shown in Unoperated condition Glass Intact Standby Condition Terminals 1 2 M S 1 and 4 5 M S 2 open Terminals 1 3 M S 1...

Page 6: ...LTD NEITHER THE WHOLE OR ANY EXTRACT MAY BE DISCLOSED LOANED COPIED OR USED FOR DRAWING TO BS8888 2000 GEOMETRIC TOLERANCES TO ISO1101 1983 SEE SHEET 1 D A H 28 08 2020 warning signals 10A Circuit shown in Unoperated condition Glass Intact Standby Condition Terminals 2 3 4 5 open Terminals 2 3 6 closed 10B Circuit shown in Operated condition Glass Broken Button pushed in Terminals 2 3 4 5 closed T...

Page 7: ...ssurance Notification Conformity to EU type based on quality assurance of the production process Module D Sira Certification Service Notified Body No 2813 CSA Group Netherlands B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment GNExCP6A GNExCP6B GNExCP6C GNExCP6D GNExCP6E II 2G Ex db eb IIC T6 Gb 40 C Ta 7...

Page 8: ...l and electronic equipment including amendment by Directive 2015 863 EU Regulation EC 1907 2006 Registration Evaluation Authorisation and Restriction of Chemicals REACH The product and all the components contained within it are free from substances of very high concern Other Standards and Regulations EN 60529 1992 A2 2013 Degrees of protection provided by enclosures IP code enclosure rated IP66 On...

Page 9: ...nt GNExCP6A GNExCP6B GNExCP6C GNExCP6D GNExCP6E II 2G Ex db eb IIC T6 Gb 40 C Ta 70 C II 2D Ex tb IIIC T75 C Db 40 C Ta 70 C or II 2G Ex db eb mb IIC T4 Gb 40 C Ta 50 C II 2D Ex tb IIIC T80 C Db 40 C Ta 50 C or II 2G Ex db eb mb IIC T4 Gb 40 C Ta 65 C II 2D Ex tb IIIC T75 C Db 40 C Ta 65 C or II 2G Ex db eb mb IIC T4 Gb 40 C Ta 70 C II 2D Ex tb IIIC T80 C Db 40 C Ta 70 C or II 2G Ex db eb mb IIC T...

Page 10: ...mity Other Standards and Regulations EN 60529 1992 A2 2013 Degrees of protection provided by enclosures IP code enclosure rated IP66 On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives regulations and standards Th...

Reviews: