background image

_______________________________________________________________________________________________________________________________ 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH 

   Tel: +44 (0)208 743 8880 

 sales@es.com    

www.e-2s.com   

 Fax: +44 (0)208 740 4200 

Document No. D202-00-201-IS_Issue_1         07-05-2019                         Sheet 1 of 8

 

INSTRUCTION MANUAL (ATEX / IECEx / CLASS DIV / UL38) 

GNExCP7-PT-S & GNExCP7-PT-D CALL POINTS 

For use in Flammable Gas Atmospheres 

1) Warnings

USE COVER BOLTS CLASS A4-70

DO NOT OPEN WHEN AN EXPLOSIVE

ATMOSPHERE IS PRESENT

POTENTIAL ELECTROSTATIC CHARGING

HAZARD

 

– SEE INSTRUCTIONS

FOR INDOOR USE

TO REDUCE THE RISK OF IGNITION OF
HAZARDOUS ATMOSPHERES, CONDUIT RUNS

MUST HAVE A SEALING FITTING CONNECTED

WITHIN 18 INCHES OF CONDUIT

AVERTISSEMENT:

UTILISER COUVRIR BOULONS CLASSE A4-70

NE PAS OUVRIR UN PRESENCE

D'ATMOSPHERE EXPLOSIVE

DANGER POTENTIEL CHARGE

ÉLECTROSTATIQUE -  VOIR LES INSTRUCTIONS

POUR USAGE INTÉRIEUR

POUR RÉDUIRE LE RISQUE D'INFLAMMATION

DES ATMOSPHÈRES DANGEREUSES, LES

CONDUITES DE CONDUIT DOIVENT AVOIR UN

RACCORD D'ÉTANCHÉITÉ RACCORDÉ À MOINS

DE 18 POUCES DE L'ENFERMEMENT

2) Rating & Marking Information

The GNExCP7PT callpoints meet the following standards for 
Fire Alarm System Use:  

UL 38 8th Edition 10/4/2013 Manual Signaling Boxes for Fire 

Alarm Systems 

ULC-S528 3rd Edition 2014-10 Manual Stations For Fire 
Alarm Systems, Including Accessories 

2.1 NEC & CEC Class / Division Ratings for US / Canada 

The GNExCP7PT callpoints comply with the following 
standards:  

UL 60079-0:2017 (Ed 6): Explosive Atmospheres - Part 0: 

Equipment - General requirements  
UL 60079-1:2015 (Ed7): Explosive Atmospheres - Part 1: 

Equipment protection by flameproof enclosures “d” 

UL 60079-31:2012 (Ed 2): Explosive Atmospheres - Part 31: 

Equipment dust ignition protection by enclosure "t" 

The Callpoints are rated as follows: 

Class I Div 2 Group ABCD T5 Ta -55°C to +70°C 
Class I Div 2 Group ABCD T6 Ta -55°C to +60°C 

Class II Div 2 Group FG T4 Ta -55°C to +70°C  

Class III Div 1 & 2 Ta -55°C to +70°C 

Installation must be carried out in compliance with the 

National Electric Code / Canadian Electric Code  

2.2 NEC Class / Zone ratings US 

The Callpoints are rated as follows: 

Class I Zone 1 AEx db IIC T5 Gb (Ta -55°C to +70°C) 

Class I Zone 1 AEx db IIC T6 Gb (Ta -55°C to +60°C) 
Zone 21 AEx tb IIIC T135°C Db (Ta -55°C to +70°C) 

Installation must be carried out in compliance with the 

National Electric Code. 

 

2.3 CEC Class / Zone ratings Canada 

The GNExCP7PT callpoints comply with the following 
standards:  

CSA C22.2 NO. 60079-0:2015 (Ed 3) Explosive Atmospheres 

– Part 0: Equipment – General requirements

CSA C22.2 NO. 60079-1:2016 (Ed 3): Explosive

Atmospheres – Part 1: Equipment protection by flameproof
enclosures “d”

CSA C22.2 NO. 60079-31:2015 (Ed 2): Explosive

Atmospheres – Part 31: Equipment dust ignition protection by

enclosure “t”

The Callpoints are rated as follows: 

Class I Zone 1 Ex db IIC T5 Gb X (Ta -55°C to +70°C) 

Class I Zone 1 Ex db IIC T6 Gb X (Ta -55°C to +60°C) 
Zone 21 Ex tb IIIC T135°C Db (Ta -55°C to +70°C)

 

Installation must be carried out in compliance with the 

Canadian Electric Code. 

 

Summary of Contents for GNExCP7-PT-D

Page 1: ...s for US Canada The GNExCP7PT callpoints comply with the following standards UL 60079 0 2017 Ed 6 Explosive Atmospheres Part 0 Equipment General requirements UL 60079 1 2015 Ed7 Explosive Atmospheres...

Page 2: ...C Area Classification Dust Zone 21 Explosive dust air mixture likely to occur in normal operation Zone 22 Explosive dust air mixture not likely to occur in normal operation and if it does it will only...

Page 3: ...osion proof Enclosure Check that the earth bonding wire between the two castings is secure and the O ring seal is in place When fitting the flameproof cover ensure the cover is sitting flat and correc...

Page 4: ...cable glands or blanking plugs The GNExCP7 Call Point range can be supplied with the following types of adapters M20 to NPT M20 to NPT M20 to M25 It is important to note that stopping plugs cannot be...

Page 5: ...Vdc and limited to a maximum total power consumption no greater than 6 224W Min resistor values and current limitations must be observed depending on supply voltage and type of components fitted If a...

Page 6: ...The plunger will remain in the down latched position until the unit is reset This is done by lifting the plunger back up using the tool reset key provided 14 Maintenance Overhaul Repair Maintenance r...

Page 7: ...1 M S 2 Optional Single or Double Microswitch Circuit shown wit Unit un operated GNExCP7 UL38 PCB Version M S 1 M S 2 7 8 1 2 3 4 5 6 M S 1 7 8 M S 1 IN M S 1 OUT Series Device if fitted 1 2 3 4 5 6 M...

Page 8: ...3 4 5 6 M S 1 Y M S 2 1 2 3 1 2 3 SERIES DEVICE 1 RESISTOR EOL DEVICE 1 EZ1 1 2 3 1 2 3 SERIES DEVICE 2 NONE DEFAULT LINK EOL DEVICE 2 RESISTOR B R M S 1 M S 2 Example Dual Microswitch Microswitch M...

Reviews: