8) Power Supply Selection

Electrical Ratings 

250Vac max. / 3.33A max 

48Vdc max. / 1.0A max 
24Vdc max / 3.0A max 

Electrical connections are to be made into the terminal blocks 

/ DIN rail provided. See Section 11 for wiring options. 

9) Selection of Cable. Cable Glands, Blanking

Elements & Adapters

For  high  ambient  temperatures  the  cable  entry  temperature 
or  the  cable  branching  point  temperature  may  exceed  60ºC 

and th

e

refore suitable heat resisting cables and cable glands 

must be used, with a rated service temperature of at least the 

values stated below: 

For Single Switch model GNExCP7-PT-S: 

For Dual Switch model GNExCP7-PT-D: 

The cable gland entries have an M20 x 1.5 entry thread. Only 

suitably rated and ATEX / IECEx certified cable glands which 

must  be  suitable  for  the  type  of  cable  being  used  and  also 
meet  the  requirements  of  the  current  Ex  ‘d’  flameproof 

installation standards EN 60079-14 / IEC60079-14. 

When only one cable entry is used the other entries must be 
closed  with  suitably  rated  and  ATEX  /  IECEx  certified 

blanking plugs. 

If  a  high  IP  (Ingress  Protection)  rating  is  required  then  a 

suitable sealing washer must be fitted under the cable glands 
or blanking plugs. 

The  GNExCP7  Call  Point  range  can  be  supplied  with  the 

following types of adapters: 

M20 to ½” NPT 

M20 to ¾” NPT 

M20 to M25 

It  is  important  to  note  that  stopping  plugs  cannot  be  fitted 

onto adapters, only directly onto the M20 entries. 

Any other adapters used must be suitably rated and ATEX / 

IECEx certified adapters. 

10) Cable Connections

Electrical  Connections  are  to  be  made  into  the  terminal 

blocks  using  solid  or  stranded  wire.  See  section  6  of  this 

manual for access to the flameproof enclosure. 

Wires  having  a  cross  sectional  area  between  0.5  mm²  to 

2.5mm²  (AWG  20  –  14)  can  be  connected  to  each  terminal 

way.  

Wiring methods shall be in accordance with CSA C22.1, 

Canadian Electrical Code, Part I, Safety Standard for 

Electrical Installations, Section 32; and CAN/ULC-S524, 

Standard for Installation of Fire Alarm Systems 

If an input and output wire is required the 2-off Live/Neutral or 

+/- terminals can be used. If fitting 2-off wires to one terminal 
way  the  sum  of  the  2-off  wires  must  be  a  maximum  cross 

sectional area of 2.5mm². 

Strip wires to 8mm. Wires may also be fitted using ferrules. 

Terminal screws need to be tightened down with a tightening 

torque of 0.45 Nm / 5 Lb-in. 

When connecting wires to the terminals great care should be 

taken  to  dress  the  wires  so  that  when  the  cover  is  inserted 

into the chamber the wires do not exert excess pressure on 

the terminal blocks. This is particularly important when using 
cables with large cross sectional areas such as 2.5mm². 

Max. ambient 

temperature 

(°C) 

55  60  65  70 

req. Cable / 

Cable Gland 

rating: (°C) 

80  85  90  95 

Max. ambient 

temperature 

(°C) 

45  50  55  60  65 

70 

req. Cable / 

Cable Gland 

rating: (°C) 

80  85  90  95  100  105 

Summary of Contents for GNExCP7-PT-D

Page 1: ...s for US Canada The GNExCP7PT callpoints comply with the following standards UL 60079 0 2017 Ed 6 Explosive Atmospheres Part 0 Equipment General requirements UL 60079 1 2015 Ed7 Explosive Atmospheres...

Page 2: ...C Area Classification Dust Zone 21 Explosive dust air mixture likely to occur in normal operation Zone 22 Explosive dust air mixture not likely to occur in normal operation and if it does it will only...

Page 3: ...osion proof Enclosure Check that the earth bonding wire between the two castings is secure and the O ring seal is in place When fitting the flameproof cover ensure the cover is sitting flat and correc...

Page 4: ...cable glands or blanking plugs The GNExCP7 Call Point range can be supplied with the following types of adapters M20 to NPT M20 to NPT M20 to M25 It is important to note that stopping plugs cannot be...

Page 5: ...Vdc and limited to a maximum total power consumption no greater than 6 224W Min resistor values and current limitations must be observed depending on supply voltage and type of components fitted If a...

Page 6: ...The plunger will remain in the down latched position until the unit is reset This is done by lifting the plunger back up using the tool reset key provided 14 Maintenance Overhaul Repair Maintenance r...

Page 7: ...1 M S 2 Optional Single or Double Microswitch Circuit shown wit Unit un operated GNExCP7 UL38 PCB Version M S 1 M S 2 7 8 1 2 3 4 5 6 M S 1 7 8 M S 1 IN M S 1 OUT Series Device if fitted 1 2 3 4 5 6 M...

Page 8: ...3 4 5 6 M S 1 Y M S 2 1 2 3 1 2 3 SERIES DEVICE 1 RESISTOR EOL DEVICE 1 EZ1 1 2 3 1 2 3 SERIES DEVICE 2 NONE DEFAULT LINK EOL DEVICE 2 RESISTOR B R M S 1 M S 2 Example Dual Microswitch Microswitch M...

Reviews: