Equipment Category:

 

2G/D 

Ambient Temperature Range:

 

 -50

°

C to +70

°

Maximum Surface Temperature for Dust Applications: 

80ºC 

6)

Location and Mounting

The  Junction  Box  should  only  be  fixed  to  services  that  can 
carry the weight of the unit. 

The  junction  box  should  be  securely  bolted  to  a  suitable 
surface  using  the  9.4mm  diameter  bolt  holes  in  the  base  of 
the unit (see figure 1). 

 
 

7)

Access to the Flameproof Enclosure

In order to connect cabling in the junction box it is necessary 
to  remove  the  flameproof  cover  to  gain  access  to  the 
flameproof chamber. To access the Ex d chamber, loosen the 
M4 grub screw on the junction box cover. Open the enclosure 
by  turning  the  junction  box  cover  counterclockwise  and 
remove  the  cover  taking  extreme  care  not  to  damage  the 
flameproof threads in the process (see figure 2). 

On  completion  of  the  installation  the  flameproof  threaded 
joints should be inspected to ensure that they are clean and 
that  they  have  not  been  damaged  during  installation. 
Flameproof  threaded  joints  are  not  intended  to  be  repaired. 
Also check that the ‘O’ ring seal is in place. When replacing 
the flameproof cover ensure the thread is engaged correctly. 
Fully  tighten  the  cover  all  the  way,  ensure  no  gap  is  visible 
between  the  cover  and  base  of  the  junction  box  enclosure. 
Tighten the M4 grub screw. 

8)

Electrical Ratings

Type No. 

Max. Power Dissipation 

GNExJ2 

5W 

9)

Cable Selection

When  selecting  the  cable  size,  consideration  must  be  given 
to  the  input  current  that  each  unit  draws  (see  table  above), 
the number of junction boxes on the line and the length of the 
cable runs. The cable size selected must have the necessary 
capacity  to  provide  the  input  current  to  all  of  the  junction 
boxes connected to the line.  

SAFETY  WARNING:  The  cable  entry  temperature  may 
70ºC or the cable branching point temperature may 
exceed  80ºC  at  high  ambient  temperatures  and  therefore 
suitable heat resisting cables and cable glands must be used, 
rated 80ºC for ambient temperatures of 70ºC. 

10)

Earthing

The  junction  box  units  must  be  connected  to  a  good  quality 
earth. The units are provided with internal and external earth 
terminals which are both located on the flameproof enclosure 
section of the unit (see figures 4 or 5).  

11)

Cable Glands

The cable gland entries have an M20 x 1.5 entry thread. Only 
suitably rated and ATEX / IECEx certified cable glands which 
must be suitable for the type of cable being used. 

When only one cable entry is used the other entries must be 
closed  with  suitably  rated  and  ATEX  /  IECEx  certified 
blanking plugs. 

If  a  high  IP  (Ingress  Protection)  rating  is  required  then  a 
suitable sealing washer must be fitted under the cable glands 
or  blanking  plugs.  A  minimum  ingress  protection  rating  of 
IP6X  must  be  maintained  for  installations  in  explosive  dust 
atmospheres. 

For combustible dust applications, the cable entry device and 
blanking elements shall be in type of explosion protection and 
shall have an IP 6X rating. 

Flameproof 
Lid Moulding 

Flameproof 
Chamber 

External 
Earth 
Stud 

Figure 1 

M3 x 6mm 
Grub Screw 

Lid Moulding

 

Figure 2 

O-Ring

 