European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           sales@e2s.com                Tel: +44 (0)20 8743 8880 

                                                                                                                                                             www.e2s.com               Fax: +44 (0)20 8740 4200 
Document No. IS 4601      Issue G                   13-01-20                       

Sheet 5 of 6

 

audible  alarm  but  be  continuously  reminded  of  the  alarm 

condition  by  the  beacon.      If  the  alarm  is  not  cleared  within 

the silence time, the sounder will be reactivated.  If the alarm 

is  cleared  during  the  silence  time  the  beacon  will  stop 

flashing,  but  the  beacon  and  the  sounder  will  both  be  re-

activated  if  the  alarm  reoccurs.  See  table  1  on  page  5  of 

these instructions for full DIP switch settings. 

 

The  silence  accept  push-button  may  be  any  mechanically 

operated switch, providing it has an IP protection suitable for 

the  environmental  conditions  to  which  it  is  subjected,  within 

the hazardous area, see section 4.5. 

 

9.  ACCESSORIES 

 

9.1   Beacon to sounder joining kit 

Comprises  an  M20  plastic  conduit  coupler  and  gasket 

enabling  the  beacon  to  be  mounted  onto  a  IS-A105N 

sounder.   This kit is supplied free of charge when a beacon 

and sounder are purchased at the same time. 

 

 

 
 
 
 

Switch settings for operation with  
IS-A105N Sounder 

 

Note when the beacon is operated on its own, 

without a sounder connected, all of the DIP 

switches should be set to OFF position. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

10. MAINTENANCE 

The  beacon  should  be  regularly  inspected  to  ensure  that  it 

has  not  been  damaged.    Frequency  of  inspection  depends 

upon  environmental  conditions,  but  initially  we  recommend 

that this should be done annually. 

 

No  attempt  should  be  made  to  repair  a  faulty  IS-L101L 

beacon. Suspect beacons must be returned to European 

Safety Systems Ltd. or to your local agent for repair

 

11. GUARANTEE 

Beacons  which  fail  within  the  guarantee  period  should  be 

returned to European Safety Systems Ltd. or our local agent.  

It  is  helpful  if  a  brief  description  of  the  fault  symptoms  is 

provided. 

 

12. CUSTOMER COMMENTS 

European Safety Systems Ltd. are always pleased to receive 
comments from customers  about our products  and  services.  
All  communications  are  acknowledged  and  whenever 
possible, suggestions are implemented.

  

 
 
 
 
 
 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

SW6 

 PS

 

SW5 
OS

 

SW4 
T4

 

SW3 
T3

 

SW2 
T2

 

SW1 

T1

 

Timer

 

Periodic sound interval when silenced, 

when SW6 is ON for (1 second every)

 

 

 

OFF

 

OFF

 

OFF

OFF

forever

 

10 secs

 

 

 

OFF

 

OFF

 

OFF

ON

 

5 secs

 

5 secs

 

 

 

OFF

 

OFF

 

ON

 

OFF

10 secs

 

5 secs

 

 

 

OFF

 

OFF

 

ON

 

ON

 

20 secs

 

5 secs

 

 

 

OFF

 

ON

 

OFF

OFF

30 secs

 

5 secs

 

 

 

OFF

 

ON

 

OFF

 

ON

 

45 secs

 

10 secs

 

 

 

OFF

 

ON

 

ON

 

OFF

1 min

 

10 secs

 

 

 

OFF

 

ON

 

ON

 

ON

 

2 mins

 

10 secs

 

 

 

ON

 

OFF

 

OFF

 

OFF

3 mins

 

30 secs

 

 

 

ON

 

OFF

 

OFF

 

ON

 

5 mins

 

30 secs

 

 

 

ON

 

OFF

 

ON

 

OFF

10 mins

 

1 min

 

 

 

ON

 

OFF

 

ON

 

ON

 

20 mins

 

1 min

 

 

 

ON

 

ON

 

OFF

 

OFF

 

30 mins

 

1 min

 

 

 

ON

 

ON

 

OFF

 

ON

 

45 mins

 

5 mins

 

 

 

ON

 

ON

 

ON

 

OFF

 

1 hour

 

5 mins

 

 

 

ON

 

ON

 

ON

 

ON

 

2 hours

 

5 mins

 

 

OFF

   

 

 

 

 Hold off mode

 – Accept Switch silences sounder for selected time.

 

ON

   

 

 

 

 One-shot mode

 — Sounder silences after either selected time, 

  or Accept Switch is pressed, whichever occurs first. 
 

The sounder is then only restored after the input power supply 
 is removed and restored.

OFF

 

 

 

 

 

 

No periodic sound while silenced

 

ON

 

 

 

 

 

 

Sound periodically while silenced

 

Summary of Contents for IS-L101L

Page 1: ...d reminder beep tone sound while the sounder is silenced The interval between the 1 second reminder beep is dependent on the timing setting for the silence period switches 1 to 4 see page 5 When the beacon is operated alone without a sounder connected all of the DIP switches should be set to the OFF position When used alone i e without a sounder connected two flash frequencies may be selected With...

Page 2: ...FE USE as stated on the IS L101L EC Type Examination Certificate SIRA 04ATEX2302X The enclosure is non conducting and may generate an ignition capable level of electrosatic charges under certain extreme conditions The user should ensure that the equipment is not installed in a location where it may be subjected to external conditions that might cause a build up of electrostatic charges on non cond...

Page 3: ...uitable for installation in an exterior location if an appropriate sealed cable entry is used 5 1 Mounting The IS L101L beacon may be secured to any flat surface using the two 6mm diameter fixing holes The lens should be aimed towards the area where maximum visibility is required 5 2 Installation procedure a Remove the beacon lens by unscrewing the two captive screws and pull the lens away from th...

Page 4: ...suitable for the environmental conditions to which it is subjected located within the same hazardous area as the beacon see section 4 5 In order that the beacon continues to produce a reasonable light output level when used in conjunction with an IS A105N sounder the power supply voltage to the barrier should be maintained at a minimum of 18V 7 ELECTRICAL SYSTEM DESIGN FOR INSTALLATION IN HAZARDOU...

Page 5: ...not been damaged Frequency of inspection depends upon environmental conditions but initially we recommend that this should be done annually No attempt should be made to repair a faulty IS L101L beacon Suspect beacons must be returned to European Safety Systems Ltd or to your local agent for repair 11 GUARANTEE Beacons which fail within the guarantee period should be returned to European Safety Sys...

Page 6: ...of the equipment should be done only with a damp cloth The IS L101L beacons are marked with the certification requirements for the ATEX and IECEx approvals e2S european safety systems ltd London W3 7QH UK www e2s com WARNING TO AVOID A POSSIBLE ELECTROSTATIC CHARGE ONLY CLEAN WITH A DAMP CLOTH IS L101L Beacon II 1G 2813 SIRA 04ATEX2302X Year Serial No 09 1000001 IECEx SIR 04 0039X Ui 28V Ii 660mA ...

Page 7: ...ngle channel barrier having parameters less than or equal to those quoted and for which the output is non ignition capable for the Class Division or Zone and Group of use 7 The IS L101L Beacon enclosure has an ingress protection rating of IP 66 If supplied without cable entry devices then metallic or plastic cable glands or conduit hubs shall be fitted that provide the required environmental prote...

Page 8: ...or equal to those quoted and for which the output is non ignition capable for the Class Division or Zone and Group of use 6 The IS L101L Beacon enclosure has an ingress protection rating of IP 66 If supplied without cable entry devices then metallic or plastic cable glands or conduit hubs shall be fitted that provide the required environmental protection 7 To prevent ignition of flammable or combu...

Page 9: ...onents may impair safety 10 C cable capacitance of cable connecting the shunt zener diode barrier to the beacon capacitance of the cable connecting the sounder to the beacon 11 The total capacitance connected to terminals of the beacon plus the total capacitance connected to terminals of the sounder i e C cable plus any other capacitance shall not exceed 83nF 12 L cable loop inductance of cable co...

Page 10: ...e sounder to the beacon 10 The total capacitance connected to terminals of the beacon plus the total capacitance connected to terminals of the sounder i e C cable plus any other capacitance shall not exceed 83nF 11 L cable loop inductance of cable connecting the galvanically isolated supply to the beacon loop inductance of cable connecting the sounder to the beacon Note CAUTION Bonding between con...

Reviews: