background image

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D199-00-201-IS

 

Issue 4

 

07-10-21

 

 

Sheet 5 of 7

 

 

NEC Class / Zone, CEC Class / Zone, and NEC & CEC Class 
/ Division installation standards: 

 
National Electrical Code, NFPA 70 or CSA 22.1 Canadian 
Electrical  Code,  Part  I,  Safety  Standard  for  Electrical 
Installations, Section 32. 

 

The installation of  the units must also be in accordance  with 
any local codes that may apply and should only be carried out 
by  a  competent  electrical  engineer  who  has  the  necessary 
training. 
 

7.2. Cable Selection and Connections 

 
When selecting the cable size, consideration must be given to 
the input current that each unit draws (see table 1), the number 
of beacons on the line and the length of the cable runs. The 
cable  size  selected  must  have  the  necessary  capacity  to 
provide the input current to all of the beacons connected to the 
line.  
 
Electrical connections are to be made into the terminal blocks 
on the PCBA, using solid wire 0.5-4mm2 / AWG 20-12 or 
stranded wire, sizes 0.5-2.5mm2 / AWG 24-14. Wire insulation 
needs to be stripped 8mm. Wires may be fitted securely with 
crimped ferrules. 
 

 

Figure 4: Wire Preparation.

 

 
Terminal screws need to be tightened down with a tightening 
torque of 0.45 Nm / 5 Lb-in. A 5-way terminal block is provided 
on  the  AC  Beacon:  2-off  Live,  2-off  Neutral  and  1-off  Earth 
terminals in total. A 4-way terminal block is provided on the DC 
Beacon: 2-off +ve and 2-off -ve terminals. 

 

Figure 5: STExB2 Entries and Terminal Block Location.

 

 
When connecting wires to the terminals great care should be 
taken to dress the wires so that when the cover is inserted into 
the  chamber  the  wires  do  not  exert  excess  pressure  on  the 
terminal  blocks.  This  is  particularly  important  when  using 
cables with large cross-sectional areas such as 2.5mm². 
 
 

Earthing 

 
Internal earthing connections should be made to the Internal 
Earth  terminal  in  the  base  of  the  housing  using  a  ring  crimp 
terminal to secure the earth conductor under the earth clamp. 
The earth conductor should be at least equal in size and rating 
to the incoming power conductors. 
 
External earthing connections should be made to the M5 earth 
stud, using a ring crimp terminal to secure the earth conductor 
to  the  earth  stud.  The  external  earth  conductor  should  be  at 
least 4mm2 in size. 
 

7.3. Cable Glands, Blanking Elements & Adapters 

 
For high ambient temperatures, the cable entry and the cable 
branching  point  temperatures  may  exceed  the  following 
temperatures: 
 

  For ATEX / IECEx: 70ºC at entry or 80ºC at branching point. 

  For NEC / CEC: 60ºC at entry or 60ºC at branching point. 

 
Therefore,  suitable  heat  resisting  cables  and  cable  glands 
must  be  used,  with  a  rated  service  temperature  at  least  as 
stated in the table below: 
 

  

Max Ambient Temperature (ºC) 

Model 

GNExB2 

15  20 

25 

30 

35 

40 

45 

50 

55 

60 

65  70 

ATEX / IECEx  /  NEC / CEC Approved 

 

 

 

 

 

 

X05DC 

 

 

 

 

 

62 

67 

72 

77 

82 

87  92 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X05AC 

 

 

 

64 

69 

74 

79 

84 

89 

94 

99  104 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X10DC 

 

61 

66 

71 

76 

81 

86 

91 

96  101  106  111 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X10AC 

 

 

62 

67 

72 

77 

82 

87 

92 

97  102  107 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ATEX / IECEx Approved 

X15DC 

 

72 

77 

82 

87 

92 

97  102  107  112  117  122 

X15AC 

 

 

 

 

74 

79 

84 

89 

94 

99  104  109 

X21DC 

 

72 

77 

82 

87 

92 

97  102  107  112  117  122 

X21AC 

73  78 

83 

88 

93 

98  103  108  113  118  123  128 

Table 2: Min. Ratings of Cables & Cable Glands. 

 

Cable Glands 

 
The cable gland entries have an M20 x 1.5 entry thread. Only 
use  suitably  rated  and  certified  cable  glands,  as  per  type  of 
approval,  which  must  be  suitable  for  the  type  of  cable  being 
used and also meet the requirements of the current flameproof 
installation standards (see section 7.1). 

 
Blanking Plugs 
 

When only one cable entry is used the other entries must be 
closed with suitably rated and certified blanking plugs as  per 
type of approval. 
 
Any unused cable entries must be closed with suitably rated 
and certified blanking plugs. 
 
 
 
 
 

Summary of Contents for STExB2X05DC012

Page 1: ...Vac 110 120Vac 50 60Hz 140mA 200mA STExB2X05AC230 230Vac 220 240Vac 50 60Hz 70mA 100mA STExB2X10DC024 SIL 24Vdc 20 28Vdc 605mA 710mA STExB2X10DC048 48Vdc 42 54Vdc 230mA 250mA STExB2X10AC115 115Vac 110...

Page 2: ...4 X15DC048 Ex db IIC T4 Gb Ta 50 C to 70 C Ex tb IIIC T127 C Db Ta 55 C to 70 C STExB2 X15AC115 X15AC230 Ex db IIC T3 Gb Ta 50 C to 70 C Ex db IIC T4 Gb Ta 50 C to 65 C Ex tb IIIC T131 C Db Ta 55 C to...

Page 3: ...th the National Electric Code Canadian Electric Code 4 Zones Gas Group Category and Temperature Classification The units can be installed in locations with the following conditions Area Classification...

Page 4: ...les to the beacon it is necessary to remove the flameproof cover to gain access to the flameproof chamber To access the Ex d chamber loosen the M4 grub screw on the beacon cover Open the enclosure by...

Page 5: ...h large cross sectional areas such as 2 5mm Earthing Internal earthing connections should be made to the Internal Earth terminal in the base of the housing using a ring crimp terminal to secure the ea...

Page 6: ...sser 8 Flash Pattern Settings 6 1 Flash Rate Setting The STExB2 beacons can produce different flash patterns as shown in Table 2 The flash patterns are selected by operation of the flash setting DIP s...

Page 7: ...Maintenance Overhaul and Repair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in accordance with the current relevant standards EN60079 1...

Page 8: ...R DIMENSIONAL TOLS STANDARDS MOD No REASON INITIAL DATE ISSUE DATE APPROVED CHECKED DATE DATE DRAWN WEIGHT Kg SURFACE FINISH MATERIAL ALTERNATIVE MATERIAL SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT S...

Page 9: ...NGULAR DIMENSIONAL TOLS STANDARDS MOD No REASON INITIAL DATE ISSUE DATE APPROVED CHECKED DATE DATE DRAWN WEIGHT Kg SURFACE FINISH MATERIAL ALTERNATIVE MATERIAL SHEET SCALE TITLE A3 IF IN DOUBT ASK DO...

Page 10: ...Netherlands B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 Gb II 2D Ex tb IIIC T...

Page 11: ...e and Place of Issue London 03 12 2021 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Reviews: