background image

TEST CONDITIONS AND LIMITS

The magnetron is tested to comply with the following electrical specification.

Test Conditions

Oscillation

Oscillation

1

2

Heater voltage (for test) .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

6.3

6.3

V

Anode current (mean)

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0

0.8

mA

Duty cycle

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

0.0005

0.0001

Pulse duration (see note 7) .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

0.5

0.05

m

s

VSWR at the output coupler

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

1.15:1

1.15:1

max

Rate of rise of voltage pulse (see note 4):

using hard tube pulser

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

200

200

kV/

m

s min

alternatively using line type pulser .

.

.

.

.

.

.

.

.

.

.

.

120

120

kV/

m

s min

Limits

Min

Max

Min

Max

Anode voltage (peak) .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

7.5

8.2

7.5

8.2

kV

Output power (mean)

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

12.5

2.5

W

Frequency (see note 8)

.

.

.

.

.

.

.

.

.

.

.

.

.

.

9350

9400

MHz

RF bandwidth at

1

/

4

power .

.

.

.

.

.

.

.

.

.

.

.

.

.

5.0

50

MHz

Frequency pulling (VSWR not less than 1.5:1)

.

.

.

.

.

.

.

23

MHz

Stability (see note 9) .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

0.1

0.1

%

Heater current .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

. see note 10

Temperature coefficient of frequency

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

. see note 11

LIFE TEST

The quality of all production is monitored by the random
selection of tubes which are then life-tested under Test
Conditions Oscillation 1. If the tube is to be operated under
conditions other than those specified herein, e2v technologies
should be consulted to verify that the life of the magnetron will
not be impaired.

End of Life Criteria
(under Test Conditions Oscillation 1)

Anode voltage (peak) .

.

.

.

.

. 7.5 to 8.5

kV

Output power (peak) .

.

.

.

.

.

.

16

kW min

RF bandwidth at

1

/

4

power .

.

.

.

.

.

5.0

MHz max

Frequency

.

.

.

.

.

.

.

9350 to 9400

MHz

Stability (see note 9) .

.

.

.

.

.

.

.

1.0

% max

NOTES

1. With no anode input power.

For average values of pulse input power greater than
40 W the heater voltage must be reduced within 3 seconds
after the application of HT according to the following
schedule:

V

h

= 0.08 (110

7

Pi) volts

where Pi = average input power in watts.

The magnetron heater must be protected against arcing by
the use of a minimum capacitance of 4000 pF shunted
across the heater directly at the input terminals; in some
cases a capacitance as high as 2

m

F may be necessary

depending on the equipment design. For further details see
the Magnetron Preamble.

2. For ambient temperatures above 0

8

C. For ambient

temperatures between 0 and

7

55

8

C the cathode pre-

heating time is 90 seconds.

3. The various parameters are related by the following

formula:

Pi = i

apk

x v

apk

x Du

where Pi = mean input power in watts

i

apk

= peak anode current in amperes

v

apk

= peak anode voltage in volts

and Du = duty cycle.

4. Defined as the steepest tangent to the leading edge of the

voltage pulse above 80% amplitude. Any capacitance in
the viewing system must not exceed 6.0 pF.

5. The maximum rate of rise of voltage for stable operation

depends upon detailed characteristics of the applied pulse
and the pulser design. The specified maximum rating applies
to typical hard tube pulsers. For minimum starting jitter and
optimum operation, the recommended rate of rise of voltage
for most line type pulsers is from 70 to 120 kV/

m

s.

6. The anode temperature measured at the point indicated on

the outline drawing must be kept below the limit specified by
means of a suitable flow of air over the anode body and
waveguide attachment brackets which serve as cooling fins.

7. Tolerance

+

40%.

8. Other frequency ranges can be supplied on request.

9. With the magnetron operating into a VSWR of 1.15:1.

Pulses are defined as missing when the RF energy level is
less than 70% of the normal energy level in a 0.5%
frequency range. Missing pulses are expressed as a
percentage of the number of input pulses applied during
the period of observation after a period of 10 minutes
operation.

10. Measured with heater voltage of 6.3 V and no anode input

power, the heater current limits are 0.43 A minimum,
0.60 A maximum.

11. Design

test

only.

The

maximum

frequency

change

with

anode

temperature

change

(after

warming)

is

7

0.25 MHz/

8

C.

MG5239T, page 2

#

e2v technologies

Summary of Contents for MG5239T

Page 1: ...ultaneously and no individual rating should be exceeded Min Max Heater voltage see note 1 5 7 6 9 V Heater starting current peak 3 0 A Anode voltage peak 7 5 8 2 kV Anode current peak 6 0 10 A Input power peak 75 kW Input power mean see note 3 85 W Duty cycle 0 0015 Pulse duration 2 0 ms Rate of rise of voltage pulse see notes 4 and 5 200 kV ms Anode temperature see note 6 120 8C VSWR at the outpu...

Page 2: ...ter directly at the input terminals in some cases a capacitance as high as 2 mF may be necessary depending on the equipment design For further details see the Magnetron Preamble 2 For ambient temperatures above 0 8C For ambient temperatures between 0 and 755 8C the cathode pre heating time is 90 seconds 3 The various parameters are related by the following formula Pi iapk x vapk x Du where Pi mean...

Page 3: ... 20 15 10 5 0 0 2 4 6 8 10 12 PEAK ANODE VOLTAGE kV PEAK OUTPUT POWER kW PEAK ANODE CURRENT A PEAK CURRENT RATING LIMITS MAXIMUM TYPICAL MINIMUM TYPICAL MINIMUM 7897 TYPICAL PERFORMANCE CHART e2v technologies MG5239T page 3 ...

Page 4: ...OTE 8 SEE NOTE 7 SEE NOTE 1 7936 OUTLINE All dimensions without limits are nominal Lead Connections Colour Element Green Heater Yellow Heater cathode Ref Millimetres A 113 11 0 38 B 104 22 0 10 C 4 318 0 076 D 4 445 0 076 E 4 368 0 41 F 32 5 0 1 G 31 0 0 1 H 25 4 max J 5 18 0 38 K 41 28 0 41 L 52 4 max M 55 55 max N 30 15 max P 101 6 max Q 46 0 min R 84 12 max S 63 5 T 12 7 max W 3 175 Y 30 99 0 1...

Page 5: ...hat adequate precautions are taken Appropriate warning labels and notices must be provided on equipments incorporating e2v technologies devices and in operating manuals High Voltage Equipment must be designed so that personnel cannot come into contact with high voltage circuits All high voltage circuits and terminals must be enclosed and fail safe interlock switches must be fitted to disconnect th...

Reviews: