Description of Functional Parameter
EC5000
Description of Functional Parameter
-
84
-
-
85
-
Read only, display AC drive power grade
0
:
total total time of accumulative when AC drive is power on
1
:
total time of accumulative when AC drive is running
C30 power selection factory defaut
:
*3
C31 time select
setting limits
:
0
~
1 factory defaut
:
1
When C32 is selected to be action total time, set C32 to be time with unit of
1 hour,and calculate time from then on.
C32 timer L setting limits
:
0H
~
9999H factory defaut
:
0H
C33 timer H setting limits
:
0
~
27*10000H factory defaut
:
0H
Set output missing test time
C29 SPO delay
setting limits
:
0.0S
~
2.0S factory defaut
:
0.2S
When the AC drive is running above the reference frequency, it’s in the filed
weaking control area, at this time, if the torque force is not enough, it’s
necessary to start frequency reduction compensation to increase the torque.
0: OFF 1: ON
C34 Frequency reduction compensation setting limits: 0
~
1 factory defaut: 1
After the operation signal is given, a delay function is added. When the
user uses AC drive to power on and operate directly, the time delay of 0-15s
can be set.
C35 Frequency reduction time setting limits: 0H
~
9999H factory defaut: 11.0S
C36 Operate delay time setting limits
:
0
~
15S factory defaut
:
0
D01 PID selection setting limits
:
0
~
3 factory defaut
:
0
0
:
without PID control
1
:
with PID control(D controls deviation)
2
:
with PID control(D controls feedback value)
3
:
with PID control(feedback value is in opposite direction)
1
.
voltage signal of control circuit terminal FV(0-10): select(A03) to be 2 or 3
to set running direction.
2
.
frequency order data(A27-A34): select(A03) to be 0 or 1 to set running
direction (combination of multi-function joint, multi-pace speed order and jog/
start order)
Set feedback value
:
■
Use current signal(4-20mA) or voltage signal(0-10V) of control circuit
terminal to set feedback value.
1
.
Current signal of control circuit terminal FI: select(B15) to be 1 to set FI
function.
2
.
Voltage signal of control circuit terminal FI: select(B15) to be 0 to set FI
function (set PC board SW1-1to be OFF)
■
Set target value
:
EC5000 AC drive can select several target value. Use voltage signal of
control circuit terminal FV or frequency order data A27-A34 to set target value.
D02 feedback increase setting limits
:
0.00
~
10.00 factory
defaut
:
1.00
D03 propotion increase setting limits
:
0.0
~
10.0 factory
defaut
:
1.0
D04 integral time setting limits
:
0.0S
~
100.0S factory
defaut
:
10.0S
D05 differential time setting limits
:
0.00S
~
1.00S factory
defaut
:
0.00S
D06 PID deviation setting limits
:
-109%
~
109% factory
defaut
:
0%
D07 integral limits setting limits
:
0%
~
109% factory
defaut
:
100%
D08 wave filting time setting limits
:
0.0S
~
2.5S factory
defaut
:
0.0S
■
F
eedback increase
:
small adjustment for PID feedback test value.
Proportion increase
:
set P control proportion increase. If set to be 0.0, no P
■
control.
Integral time
:
set I control proportion increase. If set to be 0.00, no I control.
■
Differential time
:
set D control proportion increase. If set to be 0.0, no D control.
■
PID deviation
:
deviation adjustment to frequency order control by PID, with
■
unit of 1%.
Integral limits
:
set the up limits value of frequency output controlled by I, with
■
unit of 1%.
Wave filting time
:
set the one time delay data of frequency order controlled by
■
PID