EC5000
Description of Functional Parameter
EC5000
Description of Functional Parameter
F22 U/D Step length setting limits:0.00~2.50Hz factory default:0.00Hz
When the input multi-function node choose UP/DOWN order,this
function is valid.Use the memory of the UP/DOWN order to retain the
frequency(when it is power off).Set the constant F22 to be "0".
0:keep the given value in frequency(constant A27)
1:No reserve
F23 Wire sel (Pr_F22) setting limits:0~2 factory default:0
This function is valid when use the terminal operation order. The
default is 0:
Single wire mode: connect S1 is foreward, disconnect S1 is stop
Second wires mode: connect S1 is foreward, disconnect S1 is stop,
connect S2 is reversal, disconnect S2 is stop.
Three wires mode: S1 rising along the trigger, disconnect S2 is stop,
S3 level switch and reversing.
The default is 1: Single wire mode: S1 rising along the trigger and
stop switch
Second wires mode: connect S1 is foreward, disconnect S1 is stop.
S2 level switch and reversing.
Three wires mode: S1 rising along the trigger is foreward, disconnect
S2 is stop, S3 rising along the trigger is reversal
The default is 2: Single wire mode: S1 rising along the trigger and
stop switch
Second wires mode: connect S1 is foreward, disconnect S1 is stop.
S2 rise along the pulse switch and reversing.
Three wires mode: S1 rising along the trigger, disconnect S2 is stop,
S3 level switch and reversing.
Note: Single wire mode:B01>1 Second wires mode:B01=0 Three
wires mode:B01=1
G01 fault history1 setting limits:read only factory default:NC
G02 fault history2 setting limits:read only factory default:NC
G03 fault history3 setting limits:read only factory default:NC
G04 fault history4 setting limits:read only factory default:NC
G05 fault EDC setting limits: read only factory default: NC
G06 fault voltage setting limits: read only factory default: NC
G07 fault current setting limits: read only factory default: NC
G08 fault frequency setting limits: read only factory default: NC
Only LED manipulator has this functional code.G05-G08 can display
the last fault data for the last working time, include EDC output voltage
o u t p u t c u r r e n t o u t p u t f r e q u e n c y ( O n l y r e c o r d t h e f o l l o w i n g
fault:SCUu1OCOU).
NC represents: No fault record
*1 represents: Upper limit and default value of voltage, double under
400V.
*2 represents: The rated current range of motor is 10%~200% of that
of AC drive.
*3 represents: The default value will be different according to the
capacity of AC drive.
*4 represents: read-only value.
EC5000 Series of AC drive adopts the communication protocol of Modbus
networks. Modbus can adopt two data coding modes: either ASCII (American
Standard Code for Information Interchange) or RTU (Remote Terminal Unit).
ASCII coding transmits data after converting the data into ASCII codes, while
RTU transmits data directly without conversion. The following demonstrates the
coding method of ASCII data format. Each byte is consisting of 2 ASCII
characters. For example: Value 64 Hex can be represented by “64’ in ASCII,
i.e., ‘6’ (36Hex) and ‘4’ (34Hex). The following is a mapping table of ASCII
Characters ‘0’… ‘9’, ‘A’… ‘F’.
Character
‘0’
‘1’
‘2’
‘3’
‘4’
‘5’
‘6’
‘7’
ASCII code
30H
31H
32H
33H
34H
35H
36H
37H
Character
‘8’
‘9’
‘A’
‘B’
‘C’
‘D’
‘E’
‘F’
ASCII code
38H
39H
41H
42H
43H
44H
45H