background image

2 0

 -

21

 -

  F u n c t i o n C o d e T a b l e

EC6000

 

  F u n c t i o n C o d e T a b l e

EC6000

 

P2

-

09

P2

-

10

Vector control 

over-excitation 

gain

Torque upper 
limit source 

in speed 

control mode

0

200

0: P2-11 function code setting
1: AI1   2: AI2   3: AI3
4: Pulse setting   
5: Communication setting
6:MIN(AI1,AI2)    7:MAX(AI1,AI2) 

64

0

0209H

020AH

150.0%

-

-

2000

1300

2000

1300

P2

-

11

P2

-

12

P2

-

13

P2

-

14

P2

-

15

P2

-

16

P2

-

17

020BH

020CH

020DH

020EH

020FH

0210H

0211H

 0.0

200.0%

-

-

0

60000

Digital setting 

of torque 

upper limit

Reserved

Current loop 
of M-axis Kp

Current loop 
of M-axis Ki

Current loop 
of T-axis Kp

Current loop 
of T-axis Ki

Reserved

0

P2

-

18

0212H

Speed loop 

integral 
property

0: Invalid 
1: Valid

P2

-

19

Over 

excitation 

mode selection

0213H

0: Disable 
1: Reduce process enable 
2: Constant speed and deceleration

1

P2

-

20

P2

-

21

0~1

 100~110%

0

105

%

0214H

0215H

Over 

modulation

enable 

selection

Maximum output

voltage 

cofficient

P2

-

22

0~1

 50~200%

0

100%

P2

-

23

0216H

0217H

Field 

weakening 
automatic 

adjustment 

gain

Negative 

torque

limit enable

P 3

 

V

/

F C o ntr o l Par a met e rs

Function 

Code

P3

-

00

P3

-

01

P3

-

02

P3

-

03

P3

-

04

P3

-

05

P3

-

06

P3

-

07

P3

-

08

P3

-

09

Parameter Name

V/F curve 
selection

Multi-point 

V/F frequency1 

(F1)

Multi-point 

V/F voltage1 (V1)

Multi-point 

V/F frequency2 

(F2)

Multi-point 

V/F voltage2 (V2)

Multi-point 

V/F frequency3 

(F3)

Multi-point 

V/F voltage3 (V3)

V/F Torque boost

Cut-off 

frequency of 
torque boost

V/F slip 

compensation

Address

0300H

0302H

0301H

0304H

0303H

0306H

0305H

0307H

0308H

0309H

Setting Range

0: Linear V/F       
1

Set P0-03 

~

 P3-06 parameter to obtain any 

V/F relationship curve
2: Square V/F 
3: 1.2-power V/F    4: 1.4-power V/F
6: 1.6-power V/F    8: 1.8-power V/F
9: Reserved         10: V/F complete separation 
11: V/F half separation

 0.00

P3-03

 0.0

P3-04

P3-01

P3-05

P3-02

P3-06

 P3-03

maximum frequency

 P3-04

100%

0.0

30.0%

0.00

maximum frequency

0

200.0%

Default

 

0

1.00Hz

3.0%

25.00Hz

50.0%

50.00Hz

100%

1.0%

50.00Hz

0.0%

P3

-

10

Slip compensation

time constant

030AH

0.1~10.0s

0.5s

P3

-

11

P3

-

12

0~2.00

0.64

030BH

030CH

030DH

030EH

Over excitation 

gain 

Online torque

compensation gain

80

150

100

P3

-

14

P3

-

15

P3

-

13

V/F oscillation 

suppression gain 0~1000

Model 

dependent

030DH

Oscillation 
suppression

mode selection

0~4

3

Voltage source 

for V/F 

separation 

selection

0: Digital setting (P3-15)
1: AI1             2: AI2            3: AI3
4: Pulse setting (S5)      5: Multi-reference
6: Simple PLC               7: PID
8: Communication setting

0

Summary of Contents for EC6000 Series

Page 1: ...2 1 in 2023 Copyright subject to change without notice Professional AC Drive Manufacturer ZHEJIANG EACN ELECTRONIC TECHNOLOGY CO LTD Address No 1 Jinhe Road Qinshan Street Haiyan County Jiaxing City Z...

Page 2: ...by high voltage Never connect the main circuit output terminals U V and W directly to the AC main circuit power supply The circuit board of the AC drive has CMOS IC which is extremely easy to be dama...

Page 3: ...ation Description of AC drive EC6000 Voltage 220V Voltage 380V Power kW Rated output current A 0 75 1 5 2 2 4 0 5 5 11 7 5 15 18 5 30 22 37 45 55 75 110 90 132 160 200 220 250 280 315 400 350 3 4 4 8...

Page 4: ...he CLVC mode High performance Power dip ride through Control of asynchronous motor and synchronous motor are implemented through the high performance current vector control technology The load feedbac...

Page 5: ...rip or salt Altitude Ambient temperature Lower than 1000m Display and operation on the operation panel Optional parts LCD operation panel braking unit I O extension card 1 I O extension card 2 user pr...

Page 6: ...9 D1 174 194 194 Installation Hole 4 5 6 7 9 30kW 191 120 471 450 242 232 9 0 75kW 1 5kW 2 2kW 4 0kW 5 5kW 11kW 22kW Structure A Structure 380V Class A Structure B Structure 0 75kW 105 94 160 150 137...

Page 7: ...utput Terminal Commun ication Function Description Voltage or current output is decided by P5 32 Output voltage range 0V 10V Output current range 0mA 20mA Contact driving capacity 250Vac 3A COS 0 4 30...

Page 8: ...aking unit and braking resistor Err04 Overcurrent at constant speed 1 The output circuit is grounded or short circuited 2 Motor auto tuning is not performed 3 The input voltage is too low 4 A sudden l...

Page 9: ...is damaged 4 The PG card is faulty 1 Set the encoder type correctly based on the actual situation 2 Eliminate external faults 3 Replace the damaged encoder 4 Replace the faulty PG card Err21 Err22 EE...

Page 10: ...e primary channel takes precedence Default 0 0 0 0 1 000 0 Auxiliary source Y Gain P0 06 0006H 0 000 5 000 1 000 0 Parameter Name 0008H P0 08 Digital setting of main source X frequency 0 00 Maximum ou...

Page 11: ...C Drive 55kW 0 1A P1 04 AC Drive 55kW Model dependent P1 12 P1 16 Reserved 010CH 0110H P1 23 Encoder type BIT0 Encoder type 0 ABZ incremental encoder 1 UVW incremental encoder 2 Resolver 3 SIN COS enc...

Page 12: ...05 P3 06 P3 07 P3 08 P3 09 Parameter Name V F curve selection Multi point V F frequency1 F1 Multi point V F voltage1 V1 Multi point V F frequency2 F2 Multi point V F voltage2 V2 Multi point V F freque...

Page 13: ...11 Terminal YWN 12 UP and YWN setting clear 13 Speed control Torque control switchover 14 Speed search start enable 15 Reserved 16 Multi reference terminal 1 17 Multi reference terminal 2 18 Multi re...

Page 14: ...ode after fault reset 0 The terminal operation command is valid immediately 1 The terminal operation command is valid only after it is canceled P4 16 P4 17 P4 18 Terminal protection function selection...

Page 15: ...100 00 100 00 0509H P5 10 AI2 filter time 0 00 10 00s 0 10s 050AH P5 11 AI3 input voltage minimum value 0 00 10 00V 0 00V 050BH P5 12 AI3 input voltage lower limit corresponding setting 0 00 100 00 0...

Page 16: ...0 Straight line 1 Curve 0 150 0 00 50 00Hz P6 09 P6 10 P6 11 P6 13 P6 12 P6 08 0609H 060AH 060BH 060DH 060CH 0608H 0 00Hz 0 0 0s 0 0s 00 0 Start of S curve acceleration time End of S curve acceleratio...

Page 17: ...rs Accumulated running days Accumulated running hours Read only Read only Read only Read only 070BH 0 Chinese 1 English BIT1 Output frequency display selection 0 Target frequency displays the target f...

Page 18: ...perature reached 0 100 0 65000 BIT0 Motor overload protection selection 0 Invalid 1 Valid BIT1 Ground fault duringpower on 0 Invalid 1 Valid BIT2 Input phase loss protection selection 0 Invalid 1 Vali...

Page 19: ...00 0A P9 17 Output voltage upon 2nd fault 0911H 0 3000V Read only Read only Read only Read only Read only Read only 0 3000V P9 18 AC drive status upon 2nd fault 0912H Same as P9 10 P9 19 S terminal st...

Page 20: ...2 P9 52 Protection action selection 3 0000 0934H BIT0 User defined fault 1 Err27 action selection Same as P9 50 BIT0 BIT1 User defined fault 2 Err28 action selection Same as BIT0 BIT2 Power on time ar...

Page 21: ...help to reduce PID overshoot PA 07 0A07H 00 BIT0 PID shutdown operation 0 Shutdown without calculation 1 Operation when shutdown BIT1 Constant pressure water supply sleep function 0 Invalid 1 Valid B...

Page 22: ...e first set of transmission frame selection 0 Invalid 1 Run command setting 2 Master set frequency 0031 0B09H 3 Master output frequency 4 Master upper limit frequency 5 Master set torque reserved 6 Ma...

Page 23: ...0DH 80 0 PD 13 Multi frequency 14 0D0EH 60 0 PD 14 Multi frequency 15 0D10H 10 0 PD 16 Running time of PLC reference 1 0D0FH 0000 PD 15 PLC running mode BIT0 Circulation mode 0 Stop after the AC drive...

Page 24: ...H 00 PD 39 Running direction and acceleration deceleration time of PLC reference 9 0D28H 00 PD 40 Running direction and acceleration deceleration time of PLC reference 10 0D29H 00 PD 41 Running direct...

Page 25: ...A3 03 0 Function code P5 11 setting 1 AI1 2 AI2 3 AI3 4 PULSE setting 5 Communication setting 6 MIN AI1 AI2 7 MAX AI1 AI2 The full range of 1 7 option corresponds to P5 11 A0 01 Torque setting source...

Page 26: ...48 00Hz 25 00Hz A1 11 A1 12 Add pump frequency 2 Reduce pump frequency 2 0 00 maximum frequency 0 00 A1 11 110BH 110CH 48 00Hz 25 00Hz A1 13 A1 14 Add pump frequency 3 0 00 maximum frequency 0 00 A1 1...

Page 27: ...s Application mode 1 EC6000 series AC drive has a single master and multi slave control network connected to RS485 bus When the master uses the broadcast command slave address is 0 the slave does not...

Page 28: ...ieces bytes transmit time START Sub machine address Order code Bytes quantity low position Data address 2100H high position 3 5 pieces bytes transmit time 01H 03H 06H 13H 88H 00H 00H Data address 2100...

Page 29: ...data bit the number of whole 1 in 1 1 0 0 0 1 0 1 is 4 pieces if use even verifica tion the odd even verification bit of frame will be 0 then obtain the quan tity of whole 1 still be 4 also not proce...

Page 30: ...inal control 2 RS485 control 3 Option card 4 Terminal switchover AC drive operation status 2100H R BIT0 BIT1 BIT2 BIT3 BIT4 BIT5 BIT6 BIT7 10 W Motor control mode 0 V F mode 1 SVC control 2 FVC contro...

Page 31: ...W Note 1 The function descriptions in brackets are the factory value of AC drive 2 Opticalcoupler isolation compatible ambipolarity input 3 Input impedance 2 4kO 4 Voltage range at electrical level in...

Page 32: ...uality inverter Warranty Card User Name User Address User Contact Tel Specification Number Distributor Contacts Date of delivery Address No 1 Jinhe Road Qinshan Street Haiyan County Jiaxing City Zheji...

Reviews: