  F u n c t i o n C o d e T a b l e

EC6000

 

  F u n c t i o n C o d e T a b l e

EC6000

 


5: Communication feedback
6: AI1 + AI2 

                           

7:MAX(|AI1|,|AI2|)
8:MIN(|AI1|,|AI2|)

      

  

9: Option card

 0.00

PA-05

0A02H

0A03H

2

1.00Mpa

PA

-

02

PA

-

03

PID control 

feedback 

signal source

PID digital 

feedback

Feedback 

signal gain

Feedback 

signal range

 0.00

10.000

 0

655.35

0A04H

0A05H

1.000

1.00

PA

-

04

PA

-

05

PA

-

06

0A06H

0000

PID control 
selection 1

BIT0: Feedback feature selection
0: Positive characteristic when the feedback 
signal of PID is less than the given value, 
the output frequency of AC drive will rise.
1: Negative characteristic when the feedback 
signal of PID is less than the given value, 
the output frequency of AC drive will 
decrease.
BIT1: PID parameter switching condition 
0: No switching
1: Switching through S terminal
2: Switch automatically according to 
deviation
BIT2: Integral separation
0: Invalid   1: Valid
When the multi-functional digital terminal 
integration pause is effective, the PID 
integration stops operation, and at this 
time, the PID only has the proportional and 
differential functions.
BIT3: Stop integration after output to limit 
value
0: Continue integral     
1: Stop integral
After the PID operation output reaches the 
maximum or minimum value, you can choose 
whether to stop the integration. If stop 
integral is selected, then PID integral 
stops calculation at this time, which may 
help to reduce PID overshoot. 

PA-07

0A07H

00

BIT0: PID shutdown operation
0: Shutdown without calculation
1: Operation when shutdown
BIT1: Constant pressure water supply sleep 
function
0: Invalid 1: Valid
BIT2: Reserved

       

BIT3: Reserved

PID control 
selection 2

PA-08

0A08H

20.00

0.00

100.00

Proportional 

gain Kp1

0.00~10.00s 

PA

-

09

Integral time Ti1

2.00s

0A09H

0.00~10.00s

PA

-

14

PID setting 
change time

0.00s

0A0EH

0.00~650.00s

PA

-

15

PID feedback 

filter time

0.00s

0A0FH

0.00~60.00s

PA

-

16

PID output 

filter time

0.00s

0A10H

-

PA

-

17

Reserved

-

0A11H

0.00~100.00

PA

-

18

Proportional 

gain Kp2

20.00

0A12H

0.00~10.00s 

PA

-

19

Integral 
time Ti2

2.00s

0A13H

0.00~10.000s 

PA

-

20

Differential 

time Td2

0.000s

0A14H

0.0~PA-22

PA

-

21

PID parameter 

switchover 

deviation 1

20.0%

0A15H

PA-22

PID parameter 

switchover 

deviation 2

 
PA-21~100.0%

80.0%

0A16H

0.0~100.0%

PA

-

23

PID initial value

0.0%

0A17H

0.0~6500.0s

PA

-

24

PID 

initial value 

running time

0.0s

0A18H

0.00~100.00%

PA

-

25

Maximum deviation 

between two PID 

outputs in forward 

direction

1.00%

0A19H

0.00~100.00%

PA

-

26

Maximum deviation 

between two PID 

outputs in 

reverse direction

1.00%

0A1AH

0.0~100.0%

PA

-

27

Detection value 

of disconnection 

alarm

0.0%

0A1BH

0.0~120.0s

PA

-

28

Feedback 

disconnection 

detection time

1.0s

0A1CH

0.1~100.0%

PA

-

29

Dormant judgment 

benchmark

95.0%

0A1DH

0.000~10.000s 

PA

-

10

Differential 

time Td1

0.000s

0A0AH

0.00~maximum frequency

PA

-

11

Cut-off frequency

 of PID reverse 

rotation

2.00Hz

0A0BH

0.0~100.0%

PA

-

12

PID deviation 

limit

0.0%

0A0CH

0.0~100.00%

PA

-

13

PID differential 

limit

0.10%

0A0DH

Summary of Contents for EC6000 Series

Page 1: ...2 1 in 2023 Copyright subject to change without notice Professional AC Drive Manufacturer ZHEJIANG EACN ELECTRONIC TECHNOLOGY CO LTD Address No 1 Jinhe Road Qinshan Street Haiyan County Jiaxing City Z...

Page 2: ...by high voltage Never connect the main circuit output terminals U V and W directly to the AC main circuit power supply The circuit board of the AC drive has CMOS IC which is extremely easy to be dama...

Page 3: ...ation Description of AC drive EC6000 Voltage 220V Voltage 380V Power kW Rated output current A 0 75 1 5 2 2 4 0 5 5 11 7 5 15 18 5 30 22 37 45 55 75 110 90 132 160 200 220 250 280 315 400 350 3 4 4 8...

Page 4: ...he CLVC mode High performance Power dip ride through Control of asynchronous motor and synchronous motor are implemented through the high performance current vector control technology The load feedbac...

Page 5: ...rip or salt Altitude Ambient temperature Lower than 1000m Display and operation on the operation panel Optional parts LCD operation panel braking unit I O extension card 1 I O extension card 2 user pr...

Page 6: ...9 D1 174 194 194 Installation Hole 4 5 6 7 9 30kW 191 120 471 450 242 232 9 0 75kW 1 5kW 2 2kW 4 0kW 5 5kW 11kW 22kW Structure A Structure 380V Class A Structure B Structure 0 75kW 105 94 160 150 137...

Page 7: ...utput Terminal Commun ication Function Description Voltage or current output is decided by P5 32 Output voltage range 0V 10V Output current range 0mA 20mA Contact driving capacity 250Vac 3A COS 0 4 30...

Page 8: ...aking unit and braking resistor Err04 Overcurrent at constant speed 1 The output circuit is grounded or short circuited 2 Motor auto tuning is not performed 3 The input voltage is too low 4 A sudden l...

Page 9: ...is damaged 4 The PG card is faulty 1 Set the encoder type correctly based on the actual situation 2 Eliminate external faults 3 Replace the damaged encoder 4 Replace the faulty PG card Err21 Err22 EE...

Page 10: ...e primary channel takes precedence Default 0 0 0 0 1 000 0 Auxiliary source Y Gain P0 06 0006H 0 000 5 000 1 000 0 Parameter Name 0008H P0 08 Digital setting of main source X frequency 0 00 Maximum ou...

Page 11: ...C Drive 55kW 0 1A P1 04 AC Drive 55kW Model dependent P1 12 P1 16 Reserved 010CH 0110H P1 23 Encoder type BIT0 Encoder type 0 ABZ incremental encoder 1 UVW incremental encoder 2 Resolver 3 SIN COS enc...

Page 12: ...05 P3 06 P3 07 P3 08 P3 09 Parameter Name V F curve selection Multi point V F frequency1 F1 Multi point V F voltage1 V1 Multi point V F frequency2 F2 Multi point V F voltage2 V2 Multi point V F freque...

Page 13: ...11 Terminal YWN 12 UP and YWN setting clear 13 Speed control Torque control switchover 14 Speed search start enable 15 Reserved 16 Multi reference terminal 1 17 Multi reference terminal 2 18 Multi re...

Page 14: ...ode after fault reset 0 The terminal operation command is valid immediately 1 The terminal operation command is valid only after it is canceled P4 16 P4 17 P4 18 Terminal protection function selection...

Page 15: ...100 00 100 00 0509H P5 10 AI2 filter time 0 00 10 00s 0 10s 050AH P5 11 AI3 input voltage minimum value 0 00 10 00V 0 00V 050BH P5 12 AI3 input voltage lower limit corresponding setting 0 00 100 00 0...

Page 16: ...0 Straight line 1 Curve 0 150 0 00 50 00Hz P6 09 P6 10 P6 11 P6 13 P6 12 P6 08 0609H 060AH 060BH 060DH 060CH 0608H 0 00Hz 0 0 0s 0 0s 00 0 Start of S curve acceleration time End of S curve acceleratio...

Page 17: ...rs Accumulated running days Accumulated running hours Read only Read only Read only Read only 070BH 0 Chinese 1 English BIT1 Output frequency display selection 0 Target frequency displays the target f...

Page 18: ...perature reached 0 100 0 65000 BIT0 Motor overload protection selection 0 Invalid 1 Valid BIT1 Ground fault duringpower on 0 Invalid 1 Valid BIT2 Input phase loss protection selection 0 Invalid 1 Vali...

Page 19: ...00 0A P9 17 Output voltage upon 2nd fault 0911H 0 3000V Read only Read only Read only Read only Read only Read only 0 3000V P9 18 AC drive status upon 2nd fault 0912H Same as P9 10 P9 19 S terminal st...

Page 20: ...2 P9 52 Protection action selection 3 0000 0934H BIT0 User defined fault 1 Err27 action selection Same as P9 50 BIT0 BIT1 User defined fault 2 Err28 action selection Same as BIT0 BIT2 Power on time ar...

Page 21: ...help to reduce PID overshoot PA 07 0A07H 00 BIT0 PID shutdown operation 0 Shutdown without calculation 1 Operation when shutdown BIT1 Constant pressure water supply sleep function 0 Invalid 1 Valid B...

Page 22: ...e first set of transmission frame selection 0 Invalid 1 Run command setting 2 Master set frequency 0031 0B09H 3 Master output frequency 4 Master upper limit frequency 5 Master set torque reserved 6 Ma...

Page 23: ...0DH 80 0 PD 13 Multi frequency 14 0D0EH 60 0 PD 14 Multi frequency 15 0D10H 10 0 PD 16 Running time of PLC reference 1 0D0FH 0000 PD 15 PLC running mode BIT0 Circulation mode 0 Stop after the AC drive...

Page 24: ...H 00 PD 39 Running direction and acceleration deceleration time of PLC reference 9 0D28H 00 PD 40 Running direction and acceleration deceleration time of PLC reference 10 0D29H 00 PD 41 Running direct...

Page 25: ...A3 03 0 Function code P5 11 setting 1 AI1 2 AI2 3 AI3 4 PULSE setting 5 Communication setting 6 MIN AI1 AI2 7 MAX AI1 AI2 The full range of 1 7 option corresponds to P5 11 A0 01 Torque setting source...

Page 26: ...48 00Hz 25 00Hz A1 11 A1 12 Add pump frequency 2 Reduce pump frequency 2 0 00 maximum frequency 0 00 A1 11 110BH 110CH 48 00Hz 25 00Hz A1 13 A1 14 Add pump frequency 3 0 00 maximum frequency 0 00 A1 1...

Page 27: ...s Application mode 1 EC6000 series AC drive has a single master and multi slave control network connected to RS485 bus When the master uses the broadcast command slave address is 0 the slave does not...

Page 28: ...ieces bytes transmit time START Sub machine address Order code Bytes quantity low position Data address 2100H high position 3 5 pieces bytes transmit time 01H 03H 06H 13H 88H 00H 00H Data address 2100...

Page 29: ...data bit the number of whole 1 in 1 1 0 0 0 1 0 1 is 4 pieces if use even verifica tion the odd even verification bit of frame will be 0 then obtain the quan tity of whole 1 still be 4 also not proce...

Page 30: ...inal control 2 RS485 control 3 Option card 4 Terminal switchover AC drive operation status 2100H R BIT0 BIT1 BIT2 BIT3 BIT4 BIT5 BIT6 BIT7 10 W Motor control mode 0 V F mode 1 SVC control 2 FVC contro...

Page 31: ...W Note 1 The function descriptions in brackets are the factory value of AC drive 2 Opticalcoupler isolation compatible ambipolarity input 3 Input impedance 2 4kO 4 Voltage range at electrical level in...

Page 32: ...uality inverter Warranty Card User Name User Address User Contact Tel Specification Number Distributor Contacts Date of delivery Address No 1 Jinhe Road Qinshan Street Haiyan County Jiaxing City Zheji...

Reviews: