P5
-
13
P5
-
14
AI3 input voltage
maximum value
AI3 input voltage
upper limit
corresponding
setting
050DH
050EH
0.00
~
10.00V
Same as P5-03
0.00
~
100.00%
Same as P5-04
10.00V
100.00%
P5
-
15
P5
-
16
P5
-
17
P5
-
19
AI3 filter time
HDI minimum input
frequency
Corresponding
setting of HDI
minimum input
frequency
Corresponding
setting of HDI
maximum input
frequency
050FH
0510H
0511H
0513H
0.00
~
10.00s
Same as P5-05
0.00
~
50.00KHz
This function defines the minimum frequency
accepted by the pulse input terminal HDI.
If the frequency signal is lower than this
value, the AC drive will process it
according to the input minimum frequency.
0.00
~
100.00%
It is used to set the percentage of the
setting value corresponding to the minimum
input frequency of HDI.
0.00 100.00%
~
Same as P5-17
0.10s
0.00KHz
0.00%
100.00%
P5
-
18
0512H
0.00
~
50.00KHz
Same as P5-16
50.00KHz
HDI maximum input
frequency
P5
-
20
P5
-
21
~
P5-28
HDI filter time
Reserved
0.00
~
10.00s Same as P4-11
-
0.10s
-
0514H
0515H
~
051CH
P5
-
29
A01 output
selection
051DH
0
0: Set frequency
1: Output frequency
2: Output current
3: Output voltage
4: Mechanical speed
5: Set torque
6: Output torque
7: PID setting
8: PID feedback
9: Output power
10: Bus voltage
11: Output flow
12: AI1 input value
13: AI2 input value
14: AI3 input value 15: PUL input value
16: Module temperature
17: Internal temperature
18: Excitation quantity
19: RS485 communication settings
P5
-
30
A02 output
selection
051EH
1
P5
-
31
HDO output
selection
051FH
2
P5
-
32
Analog output
signal selection
0520H
0: 0-10V
1: 4.00-20.00mA 2: 0.00-20.00mA
BIT2: HDO function enable
0: Ordinary switching value Y4 function
1: HDO high speed pulse output function
BIT3: Reserved
BIT0: AO1 signal selection
0
:
0
~
10V
1
:
4.00
~
20.00mA
2
:
0.00
~
20.00mA
BIT1: AO2 signal selection
0000
P5
-
33
P5
-
34
A01 output gain
A01 output offset
coefficient
0521H
0522H
25.0 200.0%
~
Used to adjust the value of analog output of
(AO1) terminal.
-10.0 10.0%
~
Used to adjust the zero point of the (AO1)
terminal output signal.
100.0%
0.0%
P5
-
35
P5
-
36
P5
-
37
0523H
0524H
0525H
100.0%
0.0%
0.20KHz
0.00 50.00KHz
~
When the pulse is output, the lower frequency
value of the output signal.
A02 output gain
A02 output offset
coefficient
HDO pulse output
lower limit
P5
-
38
0526H
50.00KHz
0.00 50.00KHz
~
When the pulse is output, the upper frequency
value of the output signal.
HDO pulse output
upper limit
P6
Start/Stop Control parameters
Parameter Name
Setting Range
Start mode
BIT0
:
Start mode
0: Direct start
1: First braking and then start by startup
frequency
2: Rotational speed tracking
RESTART
0.00 60.00Hz
~
Define the minimum output frequency of the
AC drive. When it is less than this frequency,
the AC drive outputs 0.00hz.
Minimum output
frequency
Function
Code
P6
-
00
P6
-
01
P6
-
02
Set the time for pre excitation of asynch-
ronous motor at startup. This parameter can
be established before starting the motor
magnetic field can effectively improve the
starting performance of the motor and reduce
the starting current and starting time.
Startup
pre-excited current
Startup
pre-excited time
Startup frequency
0.00 60.00Hz
~
It refers to the initial output frequency
when the frequency converter is started.
Setting a suitable starting frequency can
have a higher starting torque, and for some
static loads with larger static friction,
some impulse can be obtained at the moment
of starting. However, if the set value is
too large, OC1 and other faults may occur
sometimes.
P6
-
03
P6
-
04
Address
0600H
0601H
0602H
0603H
0604H
Model
dependent
0.50Hz
Default
0
0.50Hz
30
%
25.0 200.0%
~
Used to adjust the value of analog output of
(AO2) terminal.
-10.0 10.0%
~
Used to adjust the zero point of the (AO2)
terminal output signal.
0.00 50.00s
~
It refers to the time that the AC drive
keeps running under the starting frequency.
P6
-
05
0605H
0.0s
Startup frequency
holding time
-
2 1
-
-
22
-
F u n c t i o n C o d e T a b l e
EC620
EC620
F u n c t i o n C o d e T a b l e