P5

-

13

P5

-

14

AI3 input voltage 

maximum value

AI3 input voltage 

upper limit 

corresponding 

setting

050DH

050EH

0.00

10.00V

Same as P5-03

0.00

100.00%

Same as P5-04

10.00V

100.00%

P5

-

15

P5

-

16

P5

-

17

P5

-

19

AI3 filter time

HDI minimum input 

frequency

  Corresponding 

setting of HDI 

minimum input 

frequency

Corresponding 

setting of HDI 

maximum input 

frequency

050FH

0510H

0511H

0513H

0.00

10.00s  

Same as P5-05

0.00

50.00KHz

This function defines the minimum frequency 
accepted by the pulse input terminal HDI. 
If the frequency signal is lower than this 
value, the AC drive will process it 
according to the input minimum frequency.

0.00

100.00%

It is used to set the percentage of the 
setting value corresponding to the minimum 
input frequency of HDI.

0.00 100.00%

Same as P5-17

0.10s

0.00KHz

0.00%

100.00%

P5

-

18

0512H

0.00

50.00KHz

Same as P5-16

50.00KHz

HDI maximum input 

frequency

P5

-

20

P5

-

21

P5-28

HDI filter time

Reserved

 0.00

10.00s Same as P4-11

 

-

0.10s

-

0514H

0515H

051CH

P5

-

29

A01 output 

selection

051DH

0

0: Set frequency

     

 1: Output frequency

2: Output current

    

 3: Output voltage

4: Mechanical speed

  

 5: Set torque

6: Output torque

     

 7: PID setting

8: PID feedback

      

 9: Output power

10: Bus voltage

     

 11: Output flow

12: AI1 input value

 

 13: AI2 input value

14: AI3 input value  15: PUL input value
16: Module temperature
17: Internal temperature
18: Excitation quantity
19: RS485 communication settings

 

P5

-

30

A02 output 

selection

051EH

1

P5

-

31

HDO output 

selection

051FH

2

P5

-

32

Analog output 

signal selection

0520H

0: 0-10V
1: 4.00-20.00mA      2: 0.00-20.00mA 
BIT2: HDO function enable
0: Ordinary switching value Y4 function 
1: HDO high speed pulse output function
BIT3: Reserved

BIT0: AO1 signal selection
0

0

10V  

1

4.00

20.00mA 

2

0.00

20.00mA

BIT1: AO2 signal selection

0000

P5

-

33

P5

-

34

A01 output gain

A01 output offset 

coefficient

0521H

0522H

25.0 200.0%

Used to adjust the value of analog output of 
(AO1) terminal.

-10.0 10.0%

Used to adjust the zero point of the (AO1) 
terminal output signal.

100.0%

0.0%

P5

-

35

P5

-

36

P5

-

37

0523H

0524H

0525H

100.0%

0.0%

0.20KHz

0.00 50.00KHz

When the pulse is output, the lower frequency 
value of the output signal.

A02 output gain

A02 output offset 

coefficient

HDO pulse output 

lower limit

P5

-

38

0526H

50.00KHz

0.00 50.00KHz

When the pulse is output, the upper frequency 
value of the output signal.

HDO pulse output 

upper limit

P6

 

Start/Stop Control parameters

Parameter Name

Setting Range

Start mode

BIT0

Start mode

0: Direct start
1: First braking and then start by startup 
frequency
2: Rotational speed tracking 
RESTART

0.00 60.00Hz

Define the minimum output frequency of the 
AC drive. When it is less than this frequency, 
the AC drive outputs 0.00hz.

Minimum output 

frequency

Function 

Code

P6

-

00

P6

-

01

P6

-

02

Set the time for pre excitation of asynch-
ronous motor at startup. This parameter can 
be established before starting the motor
magnetic field can effectively improve the 
starting performance of the motor and reduce 
the starting current and starting time.

Startup 

pre-excited current

Startup 

pre-excited time

Startup frequency

0.00 60.00Hz

It refers to the initial output frequency 
when the frequency converter is started. 
Setting a suitable starting frequency can 
have a higher starting torque, and for some 
static loads with larger static friction, 
some impulse can be obtained at the moment
of starting. However, if the set value is 
too large, OC1 and other faults may occur 
sometimes. 

P6

-

03

P6

-

04

Address

0600H

0601H

0602H

0603H

0604H

Model 

dependent

0.50Hz

Default

 

0

0.50Hz

30

%

25.0 200.0%

Used to adjust the value of analog output of 
(AO2) terminal.

-10.0 10.0%

Used to adjust the zero point of the (AO2) 
terminal output signal.

0.00 50.00s

It refers to the time that the AC drive 
keeps running under the starting frequency.

P6

-

05

0605H

0.0s

Startup frequency 

holding time

2 1

 -

22

 -

  F u n c t i o n C o d e T a b l e

EC620

 

EC620

 

  F u n c t i o n C o d e T a b l e

Summary of Contents for EC620

Page 1: ...Drive Manufacturer EC620 Solar Pump AC Drive Electronic instruction Professional AC Drive Manufacturer ZHEJIANG EACN ELECTRONIC TECHNOLOGY CO LTD Address No 1 Jinhe Road Qinshan Street Haiyan County J...

Page 2: ...arameters 7 5 P4 Input Terminals Function 7 6 P5 Analog Terminal Parameters 7 7 P6 Start Stop Control Parameters 7 8 P7 System Configuration Parameters 7 9 P8 Auxiliary Functions 7 10 P9 Fault and Pro...

Page 3: ...pply is cut off but the indicator light of the mani pulator of AC drive is still on there is still high voltage in the AC drive which is very dangerous please do not touch the interior circuit and com...

Page 4: ...ignal PLC needs to be connected to external power supply and be disconnected from 24V power supply terminal 1 Input voltage range DC 0V 10V 2 Impedance 22k 1 Input range DC 0V 10V 4mA 20mA decided by...

Page 5: ...he startup operation is performed on the rotating motor 7 A sudden load is added during acceleration 8 The AC drive model is of too small power class 1 The output circuit is grounded or short circuite...

Page 6: ...power input is abnormal 2 The drive board is faulty 3 The lightening board is faulty 4 The main control board is faulty 1 Eliminate external faults 2 Seek technical support 3 Seek technical support 4...

Page 7: ...erform the motor autotuning 3 Set P9 40 and P9 41 correctly based on the actual situation 7 Function Code Table Function Code Table EC620 Faults and solutions EC620 P0 Standard Parameter group 0000H A...

Page 8: ...Restore default setting 0017H 3 6 Undefined 7 Initialization setting User data reset 10 Back up current user parameters 210 Restore user backup parameters 0 210 P1 Motor parameters Setting Range Func...

Page 9: ...eleration process of AC drive the overexcitation control can restrain the rise of bus voltage and avoid over voltage fault The larger the overexcitation gain the stronger the suppression effect 64 020...

Page 10: ...the gain is the more obvious the suppression of the oscillation is When using the vibration suppression function the motor rated current and no load current parameters shall be accurate otherwise the...

Page 11: ...rence ability is but the slower the response speed is the shorter the filtering time is the weaker the anti interference ability is but the faster the response speed is Filter time of terminal S1 S4 0...

Page 12: ...put signal selection AI1 input voltage minimum value BIT2 AI3 signal selection 0 0 10V 1 0 20 00ma BIT3 S8 enable HDI function 0 General switch function 1 HDI high speed pulse input function 0 00 10 0...

Page 13: ...0 200 0 Used to adjust the value of analog output of AO1 terminal 10 0 10 0 Used to adjust the zero point of the AO1 terminal output signal 100 0 0 0 P5 35 P5 36 P5 37 0523H 0524H 0525H 100 0 0 0 0 20...

Page 14: ...vibration when the machine starts stops After setting the S word characteristic time the accelera tion and deceleration time will only extend 1 2 of the S word characteristic time at the beginning and...

Page 15: ...nly BIT0 0 Stop 1 Run BIT1 0 Forward RUN 1 Reverse RUN BIT2 Reserved BIT3 Reserved AC drive status before power off P7 18 0712H Read only P8 Auxiliary Functions Function Code Parameter Name Setting Ra...

Page 16: ...of the AC drive The start up of the timer is completed by the external timer trigger terminal of the timer The timing starts from the reception to the external trigger signal After the timing time arr...

Page 17: ...HASE_INPUT 13 ERROR_LOSE_PHASE_OUTPUT 14 ERROR_OH_MODULE 15 ERROR_EXTERNAL EQUIPMENT 16 ERROR_COMMUNICATE 17 ERROR_CONTACTOR 18 ERROR_CURRENT_DETECTION 19 ERROR_AUTO TUNING 20 ERROR_ENCODER 21 ERROR_E...

Page 18: ...at instantaneous rise action 0 50s 0924H returns to normal the AC drive will acce lerate to the set frequency The basis for judging whether the bus voltage returns to normal is that the bus voltage is...

Page 19: ...the specification of no hardware detec tion input phase failure the input phase failure is detected by the change amplitude of bus voltage When the change amplitude of bus voltage is greater than P9...

Page 20: ...tial output PA 13 PID differential limit 0 10 0A0DH 0 00 650 00s PID given change time refers to the time required for PID given value to change from 0 0 to 100 0 PA 14 PID setting change time 0 00s 0...

Page 21: ...tion proportion setting Communication response delay 3 N 8 2 No check data format 8 stop bit 2 4 E 8 2 Even parity check data format 8 stop BIT 2 5 0 8 2 Odd Parity check data format 8 stop BIT 2 0 00...

Page 22: ...Multi frequency 9 0D09H PD 09 Multi frequency 10 0D0AH PD 10 Multi frequency 11 0D0BH 0 0 PD 11 Multi frequency 12 0D0CH 0 0 PD 12 Multi frequency 13 0D0DH 0 0 PD 13 Multi frequency 14 0D0EH 0 0 PD 14...

Page 23: ...ence 8 0D27H 0000 PD 39 Running direction and acceleration deceleration time of PLC reference 9 0D28H 0000 PD 40 Running direction and acceleration deceleration time of PLC reference 10 0D29H 0000 PD...

Page 24: ...12 100 00 2 00 100DH A0 13 Reserved 1009H A0 09 Minimum Error KP1 It determines the regulation intensity of the whole PID regulator The greater the P value is the greater the regulation intensity is...

Page 25: ...will be cleared and restored to the operation state 75 0 101AH A0 26 Full water level detection delay code is still valid when the switch value is full of water 5s 101BH A0 27 Wake up delay at full w...

Page 26: ...ers read only U Setting Range U Monitoring Parameters Function Code Parameter Name Default Address U 00 2110H Set frequency 1E00H AE 00 Timing time 1 AE Scheduled operation Parameters The three sets o...

Page 27: ...put Shielded twisted pair Close to AC drive ground terminal Coil Coil Shielded twisted pair Close to AC drive ground terminal Coil Shielded twisted pair Close to AC drive ground terminal Coil High spe...

Page 28: ...bias voltage and the factory value 24V port and PLC port are short circuited 3 Port S8 is restricted by function parameter P5 00 which can be used as high speed pulse input channel with maximum input...

Page 29: ...ication Number Distributor Contacts Date of delivery Address No 1 Jinhe Road Qinshan Street Haiyan County Jiaxing City Zhejiang Province Website www eacon cn E mail overseas eacon cc Warranty Service...

Reviews: