www.
eaeelectric
.com
www.
eaeelectric
.com
KO-II
MANUAL
10
www.
eaeelectric
.com
www.
eaeelectric
.com
C
D
X
Determination of Special Lengths of Offset Sizing
1-
Special length (particular or custom size)
busbars are used in places where standard
sizes do not fit when the busbar is mounted
and in other similar places. The minimum
length for these special element is 35cm.
Please measure the lengths of these modules
as shown below.
2-
Length A is measured between housing
of 2 busbars in cm. "A". The special length
is calculated by deducting 25cm from this
measured length.
X=A-25 (cm) X=Length of Special Busbar
(The busbar module will be manufactured as
per X value.)
3-
In the case in where custom-made
intermediate-size busbars are required, both
ends of the intermediate-size busbars can
be produced with or without block joints. In
such cases, please contact our company for
technical support and technical information.
Note:
Please send a drawing for combined
offsets when ordering. Indicate bolted and
non-bolted ends on the drawing.
A
Current
A
B
C
D
Aluminium
160
180
145
200
290
250
185
147
200
290
315
190
150
200
290
400
210
160
200
290
500
222
166
200
290
600
235
172
200
290
800
270
190
200
290
Copper
250
180
145
200
290
315
185
147
200
290
400
190
150
200
290
600
210
160
200
290
800
235
172
200
290
Vertical Offset
min = 200 mm
min = 200 mm
X=min:150mm
Horizontal Offset
Combined Offset
Y
B
A
A
B
Y
D
C
B
A