DCPS-6K
Maintenance & Operation Manual
Issue 2.0 Sept-2016
DCPS-6K
Maintenance & Operation Manual
12 /23
Frame Ground (FG) : min. 8SQ (8AWG) / 1 or 2 HOLE LUG (5Øx15mm)
Figure 2-2. AC Input & FG Cable Connection
2.2.2
DC Output Connection
DC output cable should be connected referring to Table 2-1 and Figure 2-3. Connect each
of the output cables to corresponding port.
Table 2-1 Output Cable & LUG
LOAD (-48V)
RTN (RETURN GROUND)
55A: 1HOLE LUG
25SQ or greater
110A: 1HOLE LUG
50SQ or greater
55A: 1HOLE LUG
25SQ or greater
110A: 1HOLE LUG
50SQ or greater
AC Ground
(PE)
PE
AC
L
AC
N
Frame Ground
(FG)
ACL (L1)
ACN (L2)