Use pliers to hold the bolt under the load cell and remove the nut. Don’t let the bolt fall through the 
deck or you will need to unbolt the scale from the floor to retrieve it.

Loosen the setscrew holding the load cell. Remove the cell.

Check the new load cell. It should have “TOP” or a “T” written on it to show which side faces up when
installed.  If not, install it so the serial number on the side is right side up. Reverse these steps to install 
the new load cell.  

After installing the nut, check to make sure the chain is not twisted.  Straighten it if needed or the 
weight readings will not track properly as gas is drained from the cylinder. 

Recalibrate the side with the new load cell.  This can be done before the lid is installed.

Troubleshooting:

If the weight goes negative when the tank is placed on the scale the load cell is upside down.  It is 
acceptable to reverse the positive and negative signal wires for that channel at the instrument or 
terminal block instead of mechanically flipping the cell over.  After fixing the problem remove the tank 
and re-zero the instrument.

“AOL” or “-AOL” on the instrument means there is a wiring problem.  Check the termial block for 
loose or broken wires.

Summary of Contents for DCS302

Page 1: ...DCS302 DUAL CYLINDER SCALE INSTALLATION OPERATION MANUAL Eagle Microsystems Inc 366 Circle of Progress Pottstown PA 19464 www eaglemicrosystems com phone 610 323 2250 fax 610 323 0114...

Page 2: ...ndependently and displays the net weight on separate digital indicators Wall mounting bracket and safety chains are optionally available These can adapt to different cylinder sizes All scales are fact...

Page 3: ...lay Instrument to a suitable and convenient wall surface Remove instrument cover and mount instrument to the wall with 10 screws or suitably sized masonry or hollow wall anchors as applicable The inst...

Page 4: ...SCALE INSTALLATION 16 30 DCS302 FOOT PRINT 2 1 2 15FT 6 CONDUCTOR CABLE WALL MINIMUM WALL CLEARANCE C L 1 5 8 RECOMMENDED ELEVATION 40 5 5 8 CHLORINE 30 1 2 CLR HOLE 4 PLCS 31 1 2 16 18 30...

Page 5: ...EI2000 INDICATOR Wall Mounting Dimensions Enclosure conforms to NEMA 4X 7 5 8 5 3 8 ctr to ctr mounting holes 5 5 8 ctr to ctr mounting holes 6 5 8 3 3 16 EI 2000...

Page 6: ...TE BLACK YELLOW Load Cell Connector Mating Half P4 A B C R T IN RS485 RS232 Com Mating Half P6 Analog 4 20 mA Output P3 RIGHT POS LEFT POS LEFT NEG RIGHT NEG CONNECTOR PLUGS EI2000 TRANSMITTER 15 CABL...

Page 7: ...Down arrow keys Once the Gross Weight display is set to the known 250 lbs the SEL PB is pressed and the display will change to Weight Remaining and show 150 lbs The weights are removed Readout should...

Page 8: ...DCS302 DUAL CYLINDER SCALE BASE SPIDER DRAWING 12 15 14 13 48 49 Not Shown 10 1 4 5 2 3 6 7 8 9...

Page 9: ...SPIDER DRAWING DMS DCS SPIDER ASSEMBLY BASE DISK 36 37 13 41 38 37 39 41 41 42 37 40 38 45 46 44 43 44...

Page 10: ...closure FG Part of Item 6 above 11 Not used 12 Screw 10B x 5 8 Self tap ss 611060 13 Pivot screw 400229 14 Disc 400178 15 Deck 400178 16 35 Not used 36 Disc washer 400154 37 Perimeter flexure 400143 3...

Page 11: ...be replaced from the terminal block Loosen the strain relief on the bottom of the divider plate and pull the wire through Load cells and adjustment bolt pictured below for reference Note how high the...

Page 12: ...o make sure the chain is not twisted Straighten it if needed or the weight readings will not track properly as gas is drained from the cylinder Recalibrate the side with the new load cell This can be...

Reviews: