ISFOLAMES LINEAR BURNER
2/2021
10
Burner Installation
IMPORTANT: Prior to installation: Shut off main gas supply to fireplace.
•
The ISOFLAMES Linear Burner system shall be installed by qualified professional service technician. To ensure proper
performance of the appliance the owner’s installation manual must be followed carefully.
•
The ISOFLAMES Linear Burner is designed to be recessed into the 2 1/2” deep firebrick cavity constructed as detailed in
Table 5
•
The burner cavity must have a height of 2-1/2”, a depth of 9-1/4”, and the length shall extend the entire width of firebox.
•
If the gas supply pipe, from the external mounted valve, is brought into the cavity through the sidewall of the firebox, the
cavity must extend to the firebox sidewall
•
For models ISF24/36/48/60LB: Gas supply shall terminate not less than 3” from sidewall.
Figure 6
•
For models ISF72/96LB: Gas supply shall terminate within than 4” from center of the cavity.
Figure 6
BURNER CAVITY DIMENSIONS (in)
Burner Model
Height
Width
Length (Min)
ISF24LB
2-1/2
9-1/4
23
ISF36LB
2-1/2
9-1/4
35
ISF48LB
2-1/2
9-1/4
47
ISF60LB
2-1/2
9-1/4
59
ISF72LB
2-1/2
9-1/4
71
ISF96LB
2-1/2
9-1/4
95
TABLE 5
FIGURE 4
FIGURE 5
Note: make sure cavity length has enough space for gas supply line.