Earthcore Industries
Isokern Maximus Linear Series See-Thru Gas Fireplace
02/2021
46
Firebrick Installation - Maximus Linear See-Thru Fireplace
1.
Lay two courses of “full” sized firebrick on floor so that the leading
edge of the coursing is aligned with opening of the firebox. Ensure
a gap of approximately ½” is kept between firebrick and sidewall to
allow for expansion.
2.
Repeat Step 1 for the opposite side of See – Thru firebox.
3.
Starting at the front edge of the unit’s sidewall, apply “split”
firebrick to the side wall of the unit. Ensure approximately ¼” gap
is kept between firebrick and damper beam/damper block
assembly to allow for expansion.
4.
Repeat on opposite side wall.
IMPORTANT:
Ensure that the required holes for the Isoflames Linear burner’s 3/8”
gas supply and pilot assembly gas and electrical connections are
drilled prior to firebrick installation.
DO NOT COVER THESE AREAS
WITH FIREBRICK!
FIGURE 25
FIGURE
FIGURE 47