Antifreeze Protection
When
HWM hydronic water modules
are applied to radiant panel hydronic heating and/or cooling
systems, the water circulating system must be protected from potential damage due to freeze-up by
utilizing an adequate antifreeze solution. The antifreeze protection is provided by the installer prior to
the EarthLinked
®
system start-up.
Propylene-glycol antifreeze solution with an inhibitor is the type of antifreeze solution required for
Earthlinked
®
products utilized in radiant panel hydronic heating and/or cooling systems. These
systems shall be freeze protected consistent with the application -specific minimum temperature, as
shown in the table below. Propylene-glycol antifreeze solutions should always be in the range of 20%
to 50% by volume, as indicated in the table.
TEMPERATURE, °F
PROPYLENE GLYCOL, %
WATER SOLUTION
MULTIPLIER FACTOR (WSMF)
18
20
x 1.03
8
30
x 1.07
-7
40
x 1.11
-29
50
x 1.16
Propylene Glycol Freeze Protection Table
Propylene-glycol can be purchased in the straight form and mixed with an inhibitor prior to filling the
system, or it can be purchased as inhibited propylene-glycol. The following are examples of
manufacturers for the above:
Straight propylene-glycol: Chemical Specialties, Inc. (
www.chemicalspec.com/spg.html
)
Inhibitor: Nu-Calgon Products, Ty-lon B20 (
www.nucalgon.com/products
)
Inhibited propylene-glycol: Houghton Chemical Corp., SAFE-T-THERM
®
,
www.houghton.com/fluids/safe-t-therm/index.html
)
IMPORTANT!
FAILURE OF THE INSTALLER TO PROVIDE ADEQUATE ANTIFREEZE
SOLUTION PROTECTION IN EARTHLINKED
®
RADIANT PANEL
HYDRONIC HEATING AND/OR COOLING SYSTEMS AT THE TIME OF
SYSTEM START-UP WILL VOID THE EARTHLINKED
®
LIMITED
WARRANTY FOR HEATING AND COOLING SYSTEMS.
IMPORTANT!
Because addition of propylene-glycol to water changes the specific heat
of water, the required flow rate of propylene-glycol solution (for the
same heat transfer as water) must be increased by the water solution
multiplier factor shown in the table above.
WARNING!
ALWAYS REMOVE THE ANODE ROD(S) FROM THE STORAGE WATER
TANK OR HEATER UTILIZED IN A RADIANT PANEL HYDRONIC
HEATING AND/OR COOLING SYSTEM. IF THE ANODE ROD(S) ARE NOT
REMOVED, THE PROPYLENE-GLYCOL SOLUTION WILL REACT WITH
THE ANODE ROD(S) TO CREATE PARTICLES THAT BLOCK FLOW AND
CAUSE SYSTEM FAILURE.
Summary of Contents for AVS-0030-A
Page 15: ...SD 410 QS H 06 15 Page 15 Figure 8a SD H Compressor Unit Electrical Ladder Diagram 230 1 60...
Page 16: ...SD 410 QS H 06 15 Page 16 Figure 8b SD H Compressor Unit Electrical Schematic Diagram 230 1 60...
Page 17: ...SD 410 QS H 06 15 Page 17 Figure 9a SD H Compressor Unit Electrical Ladder Diagram 230 3 60...
Page 18: ...SD 410 QS H 06 15 Page 18 Figure 9b SD H Compressor Unit Electrical Schematic Diagram 230 3 60...
Page 29: ...SD 410 QS H 06 15 Page 29 Figure 15 Disassembled Plug Connector...
Page 49: ...SD 410 QS H 06 15 Page 49 Figure 38 Cooling Mode Start Up...
Page 58: ...SD 410 QS H 06 15 Page 58...
Page 59: ...SD 410 QS H 06 15 Page 59...
Page 60: ...SD 410 QS H 06 15 Page 60...
Page 61: ...SD 410 QS H 06 15 Page 61...
Page 62: ...SD 410 QS H 06 15 Page 62...
Page 63: ...SD 410 QS H 06 15 Page 63...