SD-410-QS (H) (06/15)
Page 32
Once the
gland nut
has been hand tightened into the
plug body,
use two adjustable wrenches to
further tighten the
gland nut
until it is snug in the
plug body
as shown in Figure 19 and the anode
wire is held firmly in the
plug body
and will not slip out.
Do not over-tighten the gland nut!
Figure 19. Secure the Anode Wire.
After the
plug
and anode wire have been assembled, re-connect the
sealing cap assembly tool
to
the
socket
on the compressor unit cabinet. After aligning the electrical contact pins, manually
engage the threads on the
plug locking cap
with the threads on the
socket
and turn clockwise until
the
plug
is firmly hand-tightened to the
socket
as shown in Figure 20.
If the anode wire rises away
from the compressor cabinet,
be sure to shape a drip loop into the contour of the anode wire near
the
plug
and
socket.
Figure 20. The Plug and Socket Joint
After the
plug
and
socket
joint is secured, the power may be turned
ON
at the disconnect.
Summary of Contents for AVS-0030-A
Page 15: ...SD 410 QS H 06 15 Page 15 Figure 8a SD H Compressor Unit Electrical Ladder Diagram 230 1 60...
Page 16: ...SD 410 QS H 06 15 Page 16 Figure 8b SD H Compressor Unit Electrical Schematic Diagram 230 1 60...
Page 17: ...SD 410 QS H 06 15 Page 17 Figure 9a SD H Compressor Unit Electrical Ladder Diagram 230 3 60...
Page 18: ...SD 410 QS H 06 15 Page 18 Figure 9b SD H Compressor Unit Electrical Schematic Diagram 230 3 60...
Page 29: ...SD 410 QS H 06 15 Page 29 Figure 15 Disassembled Plug Connector...
Page 49: ...SD 410 QS H 06 15 Page 49 Figure 38 Cooling Mode Start Up...
Page 58: ...SD 410 QS H 06 15 Page 58...
Page 59: ...SD 410 QS H 06 15 Page 59...
Page 60: ...SD 410 QS H 06 15 Page 60...
Page 61: ...SD 410 QS H 06 15 Page 61...
Page 62: ...SD 410 QS H 06 15 Page 62...
Page 63: ...SD 410 QS H 06 15 Page 63...