SCW-410-QS (05/12)
Page 25
Figure 18. Typical Final Charge Set-up for SC, SD and SCW Compressor Units
(SC Model shown).
9. Next, the TXV is to be adjusted to provide 10°F to 20°F (or less) superheat while
running in cooling mode. The first step is to utilize the access port and LP gage in
Figure 19 to measure suction pressure.
Next, apply a thermocouple at the
compressor suction port
as shown in Figure 19, by attaching the thermocouple lead
with electrical tape, and wrapping with ½” thick insulation.