34
Fig. 4-18 Advanced parameters interface
Table 4-21 Description of advanced parameters interface
Setting item
Default Options
Description
Working mode
Normal Normal/ECO/Self-ag
e/ Parallel mode
Select the corresponding working mode
according to user needs. It is normal
working mode in general.
Parallel Number 1
1 ~ 4
Set according to the actual frame numbers
of the UPS system installed by the user.
Dev ID
1
1 ~ 16
Set device parallel ID
Output voltage
adjust
0
-5.0 ~ 5.0
Fine tune the output voltage according to
the customer's field power distribution.
Freq track limit
±
3Hz
±
0.5Hz ~
±
5Hz
Settable,
±
0.5Hz ~
±
5Hz, default
±
3Hz
Self-age
curr
precent (%)
80
30 ~ 100
It is percentage of output current in rated
output current in self-aging mode.
Summary of Contents for EA990 G5 10
Page 2: ......