3. Installation Instruction
3.1 Location
As each site has its requirements, the installation instructions in this section are to act
as a guide for the general procedures and practices that should be observed by the
installing engineer.
3.1.1 Installation Environment
The UPS is intended for indoor installation and uses forced convection cooling by
internal fans. Please make sure there is enough space for the UPS ventilation and
cooling.
Keep the UPS far away from water
,
heat and inflammable and explosive, corrosive
material. Avoid installing the UPS in the environment with direct sunlight, dust,
volatile gases, corrosive material and high salinity.
Avoid installing the UPS in the environment with conductive dirt.
The operating environment temperature for battery is 20
℃
-25
℃
. Operating above
25
℃
will reduce the battery life, and operation below 20
℃
will reduce the battery
capacity.
The battery will generate a little amount of hydrogen and oxygen at the end of
charging; ensure the fresh air volume of the battery installation environment must
meet EN50272-2001 requirements.
If external batteries are to be used, the battery circuit breakers (or fuses) must be
mounted as close as possible to the batteries, and the connecting cables should be as
short as possible.
3.1.2 Site Selection
Ensure the ground or installation platform can bear the weight of the UPS
cabinet ,batteries and battery rack
.
No vibration and less than 5 degree inclination horizontally.
The equipment should be stored in a room so as to protect it against excessive
humidity and heat sources.
The battery needs to be stored in dry and cool place with good ventilation. The most
suitable storage temperature is 20 ºC to 25ºC.
3.1.3 Size and Weight
The size of three dimensions and weight for the UPS cabinet is shown in Table 3.1
.
Attention
Ensure there is at least 0.8m before the front of the cabinet so as to easily maintain the power
module and at least 0.5m behind for
ventilation and cooling
.
Table 3.1Size and Weight for the cabinet
Configuration
Size(W*D*H)
Weight
10kVA Long Backup Type
250*680*560mm
31kg
10kVA Standard Backup Type
250*680*560mm
82kg(20pcs 9AH Batteries Included
)
15kVA Long Backup Type
250*760*700mm
33kg
15kVA Standard Backup Type
250*680*560mm
131kg(40PCS 7AH Batteries Included)