20
Enter the physical address ID setting interface by short pressing the function setting key
.
At this moment, the word “ID” is always lit up, and the numerical value showing up on the right
side of the word “ID” blinks at the same time. Select the numerical value corresponding to the ID
function by short pressing the left key
or the right key
. 1/2/3/4 address are optional.
The address is 1by default.
After selecting the address, short press the function setting key
, so as to confirm the ID
setting. At this moment, the numerical value on the right side of the word “ID” is always lit up
without blinking.
Exit the setting interface, and return back to the main interface by short pressing the function
setting key
.
4.2.2.4 Manual bypass (nbp) settings
Manual bypass setting interface
Enter the setting interface by short pressing the function setting key
. Select the function
setting by short pressing the left key
or the right key
. Select the manual bypass
setting interface, the word “nbp” blinks at this moment.
Enter the nbp setting interface by short pressing the function setting key
. At this moment,
the word “ID” is always lit up, and the “ON” or “OFF” showing up on the right side of the word
“nbp” blinks at the same time. Select whether to start using the nbp function by short pressing
the left key
or the right key
. Press “ON” to start using the nbp function. Press “OFF”
for rejection.
After selecting “ON” or “OFF”, short press the function setting key
, so as to confirm the
nbp setting. At this moment, the “ON” or “OFF” on the right side of the word “nbp” is always lit up
without blinking.
Exit the setting interface, and return back to the main interface displaying the UPS output
information by short pressing the function setting key
.
After confirming the nbp as “ON”, the UPS has bypass output after connecting with the mains
power without starting up or when the mains power is off. However, there is no backup function
after the power goes off.