5 Operation Modes
This series UPS is online double-conversion UPS system, which can be operated in the following
modes:
Mains inverter mode
Battery mode
Bypass mode
Maintenance mode (manual bypass)
Parallel redundancy mode
5.1 Mains inverter mode
Mains power provides AC power supply for the UPS rectifier. The rectifier provides DC power supply
for the inverter, and provides continuous uninterruptible AC power supply for the loads through the
inverter. The charging panel is used for battery charging.
Mains inverter mode
5.2 Battery mode
The battery mode refers to the operating mode where the batteries provide backup power supply for
the loads through the inverters. During the mains power failure, the system automatically switches to
the battery mode, and keeps on being powered by batteries until reaching the predetermined
backup time. The batteries provide output power supply through inverters. The load power supply is
uninterruptible. During the mains recovery, the system automatically switches to the mains inverter
power supply mode without any manual intervention, and the load power supply is uninterruptible. If
the mains power fails to be back to normal after reaching the battery backup time, the system will
automatically switch to uninterruptible bypass mode.