5
Voltage Transient
Recovery Time
<20ms
Output Current Peak
Ratio
3: 1
Waveform Distortion
<3% (linear load); <6% (non-linear load)
Switching Time
Mains power mode to battery mode: 0ms;
Bypass mode to inverter mode: 0ms
Overload Capacity
Load ≤105%: long time working;
105%< load ≤125%: transfer to bypass output in 10min;
125%< load ≤150%: transfer to bypass output in 1min;
150%< load ≤ 200%: transfer to bypass output in 200ms;
Load >200%: transfer to bypass output in 100ms.
Alarm
Mains Power Failure
2 beeps/s: manual silence
Battery Under Voltage
4 beeps/s: manual silence
Overload Alarm
2 beeps/s: manual silence
Fault Alarm
Long beep
System
Display
LED+LCD
Operation
Press the button
Protective Function
Output short-circuit, overload, output overvoltage / undervoltage,
battery low voltage, and overtemperature protection
Communication Port
RS232/USB (standard configuration);
RS485/SNMP card/dry contacts (options)
Operating Temperature
0~40
℃
Storage Temperature
-40~70
℃
(without batteries); -20~55
℃
(with batteries)
Relative Humidity
0~95% (non-condensing)
Operating Altitude
The altitude shall not exceed 1000m. Derating for above 1000m
according to GB/T 3859.2 standard.
Noise
<60 dB (1m)
Input / Output
Connection Mode
Terminal block
Others
MTTF
MTTF>200,000 h
MTTR
MTTR<0.5 h
Insulation Resistance
>2MΩ(500VDC)
Insulating Strength
2820Vdc, leakage current is less than1mA, 1minno arcing
Physical
Structure
Tower
IP Rating
IP20
Dimensions
W×D×H (mm)
210×5
85×59
0
310×600×880
400×815×1100
Net Weight (kg)
54
96
130
201
230
277
Color