background image

 

-18- 

2.  Press  the  function  setting  key  “

”  for  more  than  5  seconds  to  enter  the 

setting interface. Press the key “

” momentarily to select the battery end of 

discharge voltage setting interface. Press the key “

” or “

” momentarily 

to  select  the  battery  end  of  discharge  voltage.  Available  voltage  values  are 

9.6V-11.5V the end of discharge voltage is 10.2V by default.   

3.  After selecting “Confirm”, press the key “

” momentarily to save the interface 

(by  reference  to  “save  and  exit  setting”).  Press  the  key  “

”  or  “

” 

momentarily, choose “Yes”, and then press the key “

” momentarily to save 

and exit it. 

5.6    Charging current setting 

           

1.  The left figure shows the charging current  setting  interface  of  rack  UPS,  and 

the right figure shows the charging current setting interface of tower UPS. 

2.  Press  the  function  setting  key  “

”  for  more  than  5  seconds  to  enter  the 

setting interface. Press the key “

” momentarily  to  select  charging  current 

setting  interface.  Press  the  key  “

”  or  “

”  momentarily  to  select  the 

charging current. Available current values are 0A, 1A, 2A for standard  model, 

and 0A-10A, 15A, 20A for extended runtime model    the charging current is 1A 

for standard model and 10A for extended runtime model by default. 

3.  After  selecting  “Confirm”,  press  the  key  “

”  momentarily  to  save  the 

interface (by reference to “save and exit setting”). Press the key “

” or “

” 

momentarily, choose “Yes”, and then press the key “

” momentarily to save 

and exit it. 

 

-19- 

5.7    Inverter no-load shutdown function setting 

         

 

1.  The left figure shows the inverter no-load shutdown function setting interface of 

rack  UPS,  and  the  right  figure  shows  the  inverter  no-load  shutdown  function 

setting interface of tower UPS. 

2.  Press  the  function  setting  key  “

”  for  more  than  5  seconds  to  enter  the 

setting  interface.  Press  the  key  “

”  momentarily  to  select  inverter  no-load 

shutdown function setting interface. Press the key “

” or “

” momentarily 

to  select  the  inverter  no-load  shutdown  function.  The  user  can  select  ON  or 

OFF the inverter no-load shutdown function is off by default. 

3.  After  selecting  “Confirm”,  press  the  key  “

”  momentarily  to  save  the 

interface (by reference to “save and exit setting”). Press the key “

” or “

” 

momentarily, choose “Yes”, and then press the key “

” momentarily to save 

and exit it. 

5.8    Inverter no-load power saving function setting 

 

1.  The  above  figure  shows  the  inverter  no-load  power  saving  function  setting 

interface of tower UPS (tower UPS can be set through the panel). 

 

 

Summary of Contents for EA610

Page 1: ......

Page 2: ......

Page 3: ...or low above 40 or below 0 and the humidity is high above 90 4 The place having direct sun exposure or close to heating equipment 5 The place where violent vibration occurs 6 Outdoor 3 In case of fire...

Page 4: ...ials of the machine for convenience of future handling The series of products are very heavy which shall be handled with care 2 1 2 Check whether UPS is damaged during the transportation If any damage...

Page 5: ...erature of UPS shall be kept between 0 and 40 7 5 It is recommended to charge the battery for 8 hours before using it UPS will charge the battery automatically as long as the input utility power meeti...

Page 6: ...ery automatically as long as it is connected to the utility power line 3 Installation of rack UPS 9 Vertical installation Combine the connecting extensions and RT foot pieces among the accessories int...

Page 7: ...1 Press momentarily to enable inverter mute 2 In the utility power mode press momentarily to enable the battery discharge testing for 15 seconds 1 Press the key for 5 seconds to enter the setting int...

Page 8: ...ery failure utility power failure 13 3 3 LCD display functions Rack LCD Tower LCD Graphics load and battery capacity display area 1 Each grid of the load and battery capacity display area 25 capacity...

Page 9: ...el shutdown combination button for 3 seconds UPS will enter standby mode rack or bypass mode tower The yellow bypass indicator goes on Then cut off the utility power supply to shut down UPS Shutdown w...

Page 10: ...5 3 Boost charge voltage 17 1 The left figure shows the boost charge voltage interface of rack UPS and the right figure shows the boost charge voltage interface of tower UPS 2 Press the function setti...

Page 11: ...ging current is 1A for standard model and 10A for extended runtime model by default 3 After selecting Confirm press the key momentarily to save the interface by reference to save and exit setting Pres...

Page 12: ...elect ON or OFF the DC self starting function is off by default 3 After selecting Confirm press the key momentarily to save the interface by reference to save and exit setting Press the key or momenta...

Page 13: ...to exit the state of automatic page up down 1 Output Display UPS output voltage and output frequency as shown below the left figure shows the display interface of rack UPS and the right figure shows...

Page 14: ...shutdown It can be set 3 load to shut down after 80s transfer time 10ms THDV resistive load 5 Inductive load Yes Capacitive load Yes Resistive load Yes Protection Overload short circuit battery low v...

Page 15: ...collected too much dust or not 4 Check whether the input output and battery cables are firm or not and whether the cable insulation is good or not 5 Ensure UPS is well protected against moisture 6 St...

Page 16: ...battery terminals are firmly fastened 29 9 Exception Handing Carry out the self checking according to the following methods in case of abnormal conditions If the abnormal condition cannot be eliminat...

Reviews: