background image

 

-28- 

2. 

Maintain the load condition, and record the total power. Disconnect UPS input 

plug (to simulate the interruption of utility power). UPS enters battery discharge 

mode, until it is shut down automatically. And record the discharge time. Keep 

the record of initial discharge time for future use. 

a)  The total load capacity (power consumption) shall be calculated by watts 

(W).   

b)  If the nameplate only states the volt-ampere (VA) value, multiply it by the 

power factor (0.8, if not stated) and convert it to watts (W). 

c)  If only the current (A) value is stated, multiply it by the rated voltage (V) 

and then by the power factor, and convert it to watts (W). 

3. 

The battery service life is about 1 – 2 years in normal service conditions. When 

the temperature is pretty high and the discharge  is  conducted  frequently,  the 

battery service life may be 0.5 – 1 year. 

4. 

The battery performance decreases gradually  (marked  by  the  discharge  time) 

as the application period extends. When the discharge time decreases to 80% 

of initial value, its performance reduction will be accelerated. Accordingly, the 

battery  checking  time  shall  be  changed  to  once  per  month  from  once  half  a 

year. 

5. 

Battery maintenance of extended runtime model (it is crucial to conduct proper 

maintenance  for  the  battery  to  prevent  the  precision  equipment  from  being 

damaged in case of power outage).   

a)  Clean the dust and dirt on the battery. 

b)  Check internal lines of all batteries for any looseness or corrosion. Carry 

out the replacement and repair if necessary. 

c)  Ensure the battery and battery terminals are firmly fastened. 

 

 

 

 

 

 

 

-29- 

9.    Exception Handing 

Carry  out  the  self  checking  according  to  the  following  methods  in  case  of  abnormal 

conditions.  If  the  abnormal  condition  cannot  be  eliminated,  please  contact  the  nearest 

distributor or warranty unit or directly contact our company. 

Condition 

Confirmation and countermeasures 

The utility power is normal, while UPS 

cannot connect to it 

1) 

Check whether the power cord is loose. 

2) 

Check whether the over-current protector is out. 

The utility power is normal, while UPS cannot 

start normally. The failure indicator is normally 

on, “

!

” icon is normally on, and LCD function 

display area displays OFF 

1) 

Check whether the battery wire is connected or 

not. 

2) 

Confirm whether the battery is damaged or not. 

In utility mode, the buzzer beeps continuously, 

”  icon  blinks,  and  the  machine  works  in 

bypass  mode  after  a  while    in  inverter  mode, 

the  buzzer  beeps  continuously,  “

”  icon 

blinks,  and  the  machine  is  shut  down 

automatically after a while 

Output overload check whether the condition 

of overload occurs in UPS load display. 

Reduce the load. 

UPS cannot power on after the “ON” key is 

pressed 

1) 

The “ON” key is pressed  too  briefly.  Press  the 

“ON” key continuously for more than 3 seconds 

to start UPS. 

2) 

Check whether the battery is connected. 

3) 

UPS  has  internal  failure.  Please  contact  the 

supplier. 

The battery discharge time diminishes 

1) 

The  battery  has  not  been  fully  charged.  Keep 

UPS connected to  utility  power  persistently  for 

more than 8 hours to charge the battery again. 

2) 

UPS  is  overloaded.  Check  load  capacity,  and 

reduce the load. 

3) 

The  battery  is  aged  and  the  capacity 

decreases.  Replace  the  battery.  Please 

contact  the  supplier  to  obtain  the  battery  and 

components for replacement. 

 

Summary of Contents for EA610

Page 1: ......

Page 2: ......

Page 3: ...or low above 40 or below 0 and the humidity is high above 90 4 The place having direct sun exposure or close to heating equipment 5 The place where violent vibration occurs 6 Outdoor 3 In case of fire...

Page 4: ...ials of the machine for convenience of future handling The series of products are very heavy which shall be handled with care 2 1 2 Check whether UPS is damaged during the transportation If any damage...

Page 5: ...erature of UPS shall be kept between 0 and 40 7 5 It is recommended to charge the battery for 8 hours before using it UPS will charge the battery automatically as long as the input utility power meeti...

Page 6: ...ery automatically as long as it is connected to the utility power line 3 Installation of rack UPS 9 Vertical installation Combine the connecting extensions and RT foot pieces among the accessories int...

Page 7: ...1 Press momentarily to enable inverter mute 2 In the utility power mode press momentarily to enable the battery discharge testing for 15 seconds 1 Press the key for 5 seconds to enter the setting int...

Page 8: ...ery failure utility power failure 13 3 3 LCD display functions Rack LCD Tower LCD Graphics load and battery capacity display area 1 Each grid of the load and battery capacity display area 25 capacity...

Page 9: ...el shutdown combination button for 3 seconds UPS will enter standby mode rack or bypass mode tower The yellow bypass indicator goes on Then cut off the utility power supply to shut down UPS Shutdown w...

Page 10: ...5 3 Boost charge voltage 17 1 The left figure shows the boost charge voltage interface of rack UPS and the right figure shows the boost charge voltage interface of tower UPS 2 Press the function setti...

Page 11: ...ging current is 1A for standard model and 10A for extended runtime model by default 3 After selecting Confirm press the key momentarily to save the interface by reference to save and exit setting Pres...

Page 12: ...elect ON or OFF the DC self starting function is off by default 3 After selecting Confirm press the key momentarily to save the interface by reference to save and exit setting Press the key or momenta...

Page 13: ...to exit the state of automatic page up down 1 Output Display UPS output voltage and output frequency as shown below the left figure shows the display interface of rack UPS and the right figure shows...

Page 14: ...shutdown It can be set 3 load to shut down after 80s transfer time 10ms THDV resistive load 5 Inductive load Yes Capacitive load Yes Resistive load Yes Protection Overload short circuit battery low v...

Page 15: ...collected too much dust or not 4 Check whether the input output and battery cables are firm or not and whether the cable insulation is good or not 5 Ensure UPS is well protected against moisture 6 St...

Page 16: ...battery terminals are firmly fastened 29 9 Exception Handing Carry out the self checking according to the following methods in case of abnormal conditions If the abnormal condition cannot be eliminat...

Reviews: