9
Model
Battery Quantity (unit)
Battery Voltage (volt)
1kVAH
3
36
2kVAH
6
72
3kVAH
8
96
One end of battery cable is for UPS terminals while the other end with triple cables
is for battery terminals. Correct installation procedure is highly vital or else probable
electric shock will arise. Users are strictly required to follow the below procedure.
Connect batteries correctly and make sure the total battery voltage is available for
UPS.
Correctly connect the long battery cable to battery terminals first, red wire is to
positive plate while black is to negative. If users connect the UPS first, electric
shock or other danger may not be avoided.
Before connecting loads, users should supply mains power and energize the UPS.
Connect long battery cable to UPS terminals with correct poles link (red is for ‘+’,
black is for ‘-‘), UPS will start charging automatically.
Connect the battery pack to the battery connector.