3 Installation
21
Fig. 3-3 Remove four baffles
Step 2:
remove the screws between the equipment and the bottom pallet. See Fig. 3-4 (take 400 kVA/500
kVA/600 kVA model as an example).
Fig. 3-4 Remove pallet screws
Step 3:
lift the cabinet with an automatic fork lift truck and when the bottom of the cabinet is about 5mm away
from the pallet, remove the pallet. Pay attention to the center of gravity. The center of gravity of 200 kVA/250
kVA/300 kVA UPS model is shown in Fig. 3-5, and center of gravity of 400 kVA/500 kVA/600 kVA UPS model is
shown in Fig. 3-6.
The cabinet must be lifted by the forklift, otherwise the cabinet may be damaged.
When the forklift is used from the front, and the arm length of the forklift should be larger than the width of
the equipment. The forklift shall have the arm with more than 200mm internal width and less than 700mm
outer diameter for 200 kVA/250 kVA/300 kVA UPS and the arm with more than 700mm internal width and
less than 1300mm outer diameter for 400 kVA/500 kVA/600 kVA UPS.
When the forklift is used from the side, the arm of the forklift should be larger than the length of the forklift,
the inner width of the arm should be larger than 200mm, and the outer diameter should be less than 600mm.
The lifting weight of the forklift should be greater than the equipment weight.
CAUTION
Baffles
Baffles
Pallet screw
Rear pallet screw
Summary of Contents for EA990 Super