User Manual 200 kVA-1200 kVA UPS
4 Monitoring Display Interface
63
Setting item
Default
Settable value
Description
EOD restart
Enable
Disable/Enable
The system supplies the power by the battery inverter after
failure of the mains. If it is set to Enable, when the system
stops due to voltage under-voltage (EOD), the bypass
power supply is not valuable, and the system output is
powered down, the system will be automatically restarted
upon recovery of the mains. If it is set to Disable, the user
is required to manually clear the fault, manually start the
system, or set to the enabling by modification of EOD
self-recovery after shutdown setting
EOD restart delay
(min)
10
1 ~ 1440
If “EOD restart” is set to Enable, when the power of the
system EOD fails and is recovered, after the set delay, the
system will automatically start the inverter output.
Forced bypass
Off
Off/On
If it is set to be on, although the bypass voltage is
abnormal, the UPS system supplies the power in the
bypass mode when the UPS system requires supply of the
power by the bypass output. When the bypass is extra-high
voltage, the system cannot supply the power in the bypass
mode.
Impact to bypass On
On/Off
If it is set to be on, when the output voltage of the UPS
system is decreased quickly due to impact load, the system
will supply the power in the bypass mode for a short time.
EPO function
On
On/Off
Set whether to enable emergency shutdown function
according to the actual requirements of customers
EPO action
To bypass
To bypass/
Shutdown
According to the customer's actual requirements, when
EPO alarm is triggered, the corresponding action of UPS
system is to switch to the bypass or disconnect the output.
Under normal circumstances, please choose output
disconnected
Maint.cover plate On
On/Off
If it is set to On, the system will test the installation status
of the maintenance cover plate
Short action
To bypass
To bypass/
Shutdown
When the output of the UPS system is shorted, the UPS
system will switch to the bypass or disconnect the output
Bypass overload
action
Shutdown Shutdown/None
After the bypass overload time, the UPS system will
disconnect the output or do not work. This setting may be
changed with the authorization of the manufacturer,
otherwise, the warranty will come invalid. If selected to
“None”, it is possible to cause damage to the bypass device
due to failure to timely protect the bypass.