background image

DIMENSIONS

— 2 —

ENVIRONMENTAL

Operating Temperature Range

40

°

F

100

°

F

Operating Humidity Range

RH40% - RH95%

MECHANICAL

Weight

125 lbs (without packaging)

Drain Size

5/8"

Capacity

320 Pints @ 86

°

F, 80% RH

Airflow

790 CFM (free flow)

ELECTRICAL

Voltage

208~230 VAC ~, 1ø, 60 HZ

Operating Current

7.0A @ 86

°

F, 80% RH

Efficiency

3.5 L/kW-hr (6.9 pints/kW-hr) @
86

°

F, 80% RH

SPECIFICATIONS

Summary of Contents for SDD-150L

Page 1: ...DEHUMIDIFIER SDD 150L INSTRUCTION MANUAL...

Page 2: ...SAFTY INSTRUCTIONS 1 SPECIFICATIONS 2 UNPACKING THE DEHUMIDIFIER 3 INSTALLATION GUIDE 4 OPERATION GUIDE 6 STRUCTURE AND RUNNING 7 OVERALL PARTS 8 NORMAL MALFUNCTION REMOVAL 9 DIRECTORY...

Page 3: ...not necessary to use dehumidifier when the room temperature is below 10 the absolute humidity is quite low at this condition 5 Please try to seal environment better to increase the effect of dehumidif...

Page 4: ...umidity Range RH40 RH95 MECHANICAL Weight 125 lbs without packaging Drain Size 5 8 Capacity 320 Pints 86 F 80 RH Airflow 790 CFM free flow ELECTRICAL Voltage 208 230 VAC 1 60 HZ Operating Current 7 0A...

Page 5: ...Automatic defrost protection function The dehumidifier will defrost automatically when freezing occurs The dehumidifier will start automatically when defrost process is complete Default defrost setti...

Page 6: ...ng to the position of install hole on the machine then install the expansion screw to fix the thread rod B Install the machine through the four thread rods and adjust the height according the space to...

Page 7: ...to fix the dehumidifier on the ceiling 3 Ensure the installation of dehumidifier is horizontal to avoid malfunction or leakage 4 Ensure drain tube is installed unhindered without overmuch bends 5 Ens...

Page 8: ...d with a little diluted neutral detergent 3 Filter Cleaning it will affect the dehumidifying effect or cause malfunction if accumulate dust on filter it needs to be cleaned regularly clean it at least...

Page 9: ...ith 1 RH scale in running mode Press the key to set the hour or minute down with 1 hour or 1 minute scale in timed on off or clock setting mode 5 Humi Press the key to set the humidity value down with...

Page 10: ...Heat exchanger 13 Base bracket 4 Heat exchanger cover 14 Power cord pressing block 5 Top plate 15 Electrical box 6 High pressure pipe 16 Main control board 7 Low pressure pipe 17 Connection terminal 8...

Page 11: ...2 POWER OFF 3 POWER IS NOT PLUG IN 4 BLOWN FUSE 1 RESUME POWER 2 POWER ON 3 PLUG IN 4 REPLACE FUSE BAD DEHUMIDIFICATION EFFECT 1 FILTER BLOCKED WITH DUST 2 AIR INLET IS BLOCKED 3 USED IN BAD SEALED RO...

Page 12: ......

Reviews: