background image

To order parts and supplies: 800.343.9353  >>  eastwood.com 

13

TROUBLESHOOTING

PROBLEM

CAUSE

CORRECTION

Oil/Water Mist 

Spraying from 

Under Pres-

sure Switch

The unit is collecting excess water in 

the moisture filter #31716 and oil tank 

which is raising oil level and resulting in 

oil/water being forced into the white ny-

lon discharge hose going to the unloader 

valve under the pressure switch.

Refer to 

OIL TANK CONDENSATION DRAIN

 for preventing condensation build up 

by draining it regularly.

Unit Does Not 

Turn On or Run

No power to unit or defective pressure 

switch.

Check breaker is not tripped. If breaker is Ok – disconnect unit from power.  

Check Continuity across switch terminals. A good switch will show continuity 

across both sets of terminals, if one set of terminals is OPEN switch is bad. 

Replace pressure switch #32207.

Motor Runs 

Slow or Hard 

to Start

Improper Supply Voltage/Circuit.

Assure unit has actual 208/240 on min 30-amp circuit and not 120VAC.

Defective start and/or run capacitor.

Disconnect unit from power. 

• Remove Motor Electric Box Cover (on top of motor). 

• Look at both capacitors for leaking oil, black soot, bloated or cracked cases. 

• If defective- replace capacitors and motor controller.
Replace Start Capacitor #32213.
Replace Run Capacitor #32214.
Replace Motor Controller #32215.

Air Discharges 

From Under 

Pressure 

Switch When 

Unit Shuts Off 

at 145 PSI

The Unloader Valve is located below the 

Pressure Switch and is in place to relive 

air pressure from the Scroll Pump and 

Oil Tank. This discharge will last up to 

20 seconds and is necessary to relive 

air pressure in the Pump before next 

cycle starts to eliminate starting against 

a head pressure.

This is normal operation.

Overpressure 

Relief Valve 

Opens. Unit 

Will Not Shut 

Off.

Pressure Switch is stuck in “ON” 

position- unit will continue to run even 

if pressure switch knob is turned to 

“OFF”. Unit will continue to vent through 

Overpressure Relief Valve.

Replace Pressure switch #32207.

Motor Makes 

Loud Metallic 

Grinding Noise

Motor is defective from either bearing 

failure, oil starvation or overheating.

Replace the following item: 

Motor/Pump assembly #32208.

Squeaking/

Chatter Noise 

at Air Filter 

When Unit 

Starts

Aluminum cylinder below air filter hous-

ing is the Intake Check valve. The valve 

seal is making the noise.

It will not harm or hinder performance of unit and will cease after a few cycles.

Summary of Contents for QST 30

Page 1: ...QST 30 60 SCROLL COMPRESSOR INSTRUCTIONS Item 63600...

Page 2: ...Assembly SPECIFICATIONS Power Requirement 208 240V 60Hz Single Phase Full Load Amps 17 Motor Horsepower 4 hp Tank Size 26 4 gallon 100 liter Tank Fill Time 3 minutes max Air Delivery 12 7 SCFM 90 PSI...

Page 3: ...eaker or disconnect power supply before servicing the compressor and when the compressor is not in use Never direct high pressure airstream to exposed flesh This compressor must be located only on a f...

Page 4: ...e pressure of this unit Personal injury and or property damage may result if the relief valve is tampered with Use only hose pipe and fittings rated for compressed air distribution lines Do not use pl...

Page 5: ...ood Synthetic Scroll Compressor Oil to the fill port of the Oil Reservoir using a suitable funnel FIG 5 Check the condition of the Seal then replace Oil Fill Plug Dipstick and tighten securely Before...

Page 6: ...ting and low voltage at the Compressor during startup and running Low voltage will cause difficult starting overheating and excessive tripping of circuit breakers The wire gauge must be increased for...

Page 7: ...at during operation Use caution when servicing to avoid burns If any air or oil leaks are discovered call Eastwood Tech at 1 800 343 9353 or email at tech eastwood com INJURY HAZARD Before performing...

Page 8: ...l Separator in a well planned air line layout after the Air Outlet Valve COMPRESSOR LOCATION POSITIONING Locate all sides of the Compressor no less than 1 foot 0 3m away from any wall or closure Maint...

Page 9: ...Switch to the OFF position Release pressure from Tank until Tank Pressure Gauge indicates 0 PSI Disconnect Compressor from power supply Allow the unit to sit at least 8 hours without operating This al...

Page 10: ...cool a minimum of 1 hour after last use before servicing to avoid burns INJURY HAZARD Before performing any service turn Power Switch to the OFF position FIG 1 Shut off breaker or disconnect power su...

Page 11: ...and securely position it above a suitable drain pan then slowly open the Drain Valve TIP It is advisable to place spacers under the opposite side Casters lifting the Compressor slightly on that end t...

Page 12: ...URY HAZARD Before performing any service turn Power Switch to the OFF position FIG 1 Shut off breaker or disconnect power supply Oil Filter 31715 Moisture Separator 31716 FIG 15 FIG 15 Used Oil is a p...

Page 13: ...th capacitors for leaking oil black soot bloated or cracked cases If defective replace capacitors and motor controller Replace Start Capacitor 32213 Replace Run Capacitor 32214 Replace Motor Controlle...

Page 14: ...mately disappear as a film of oil will coat inside of tank during use see page 9 Unit Will Not Reach 145 PSI Shuts Off Early Defective Pressure gauge Replace pressure gauge with known good gauge and r...

Page 15: ...To order parts and supplies 800 343 9353 eastwood com 15 NOTES...

Page 16: ...5 Replacement Eastwood Oil Filter 31716 Replacement Eastwood Moisture Separator 31718 Eastwood Synthetic Scroll Compressor Oil 1 Quart 0 946 liter 32207 Replacement Pressure Cut off Switch 32213 Repla...

Reviews: