GT200 series general purpose inverter instruction manual
(2)Table2-3 The selection of main circuit cable diameter, protection circuit breaker QF or fuse
as following
Model
Circuit breaker
(
A
)
Fuse
(
A
)
Input/output
wire
(
mm
2
)
Control wire
(
mm
2
)
GT200-4T0007G
10
10
1.5
1
GT200-2S0007G
10
10
1.5
1
GT200-4T0015G
10
10
1.5
1
GT200-2S0015G
20
16
1.5
1
GT200-4T0022G
16
10
2.5
1
GT200-2S0022G
32
20
2.5
1
GT200-4T0040G
20
16
2.5
1
GT200-4T0055G/4T0075P
25/40
25/32
4/6
1.0
GT200-4T0075G/4T0110P
40/63
32/38
6/10
1.0
GT200-4T0110G/4T0150P
63/63
38/40
10/10
1.0
GT200-4T0150G/4T0185P
63/100
40/50
10/16
1.0
GT200-4T0185G/4T0220P
100/100
50/65
16/16
1.0
GT200-4T0220G/4T0300P
100/125
65/80
16/25
1.0
GT200-4T0300G/4T0370P
125/160
80/95
25/25
1.0
GT200-4T0370G/4T0450P
160/200
95/115
25/35
1.0
GT200-4T0450G/4T0550P
200/200
115/170
35/35
1.0
GT200-4T0550G/4T0750
200/250
170/205
35/70
1.0
GT200-4T0750G/4T0900P
250/315
205/245
70/70
1.0
GT200-4T0900G/4T1100P
315/400
245/300
70/95
1.0
GT200-4T1100G/4T1320P
400/400
300/300
95/150
1.0
GT200-4T1320G/4T1600P
400/630
300/410
150/185
1.0
GT200-4T1600G/4T1850P
630/630
410/475
185/240
1.0
GT200-4T1850G/4T2000P
630/630
410/475
185/240
1.0
GT200-4T2000G/4T2200P
630/800
475/475
240/150×2
1.0
GT200-4T2200G/4T2500P
800/800
475/620
150×2/150×2
1.0
GT200-4T2500G/4T2800P
800/1000
620/620
150×2/150×2
1.0
GT200-4T2800G/4T3150P
1000/1000
620/800
185×2/185×2
1.0
22