GT200 series general purpose inverter instruction manual
RA
RB
RC
Programmable
relay output
terminal
Normal
:
RA-RB normally
closed
;
RA-RC normally
open
;
Action
:
RA-RB normally
open
;
RA-RC normally
closed
(
Detail refer to F6.34
)
Rating of contact
NO
:
5A 250VAC
NC
:
3A 250VAC
Remark: By extend card
Analog
input
AI1
Analog input
AI1
Accept the input of analog
voltage
(Reference ground
:
GND)
Input voltage range
:
0
~
10V (input impedance
:
100KΩ)
Resolution
:
1/1000
AI2
Analog input
AI2
Accept input of analog
current and voltage
(Reference ground
:
GND)
Selected by Jumper pin J3
Input current range
:
0
~
20mA
(input impedance
:
165Ω)
Resolution
:
1/1000
AI3
Analog input
AI3
Accept differential analog
voltage input
、
PT100/PT1000 input
(
Reference ground
:
P_GND
)
Input voltage range
:
-10V~+10V
(
Remark: By extend
card
)
Analog
output
AO1
Analog output
Provide analog voltage
output, Corresponding to
12 kinds of physical
quantities,output
frequency as factory
default
(
refer to F6.24/F6.27
)
Voltage output range
:
0
~
10V
Current output range
:
0
~
20mA
AO2
Analog output
Provide analog voltage
output, Corresponding to
12 kinds of physical
quantities,output
frequency as factory
default
(
refer to F6.25/F6.28
)
Voltage output range
:
0
~
10V
Current output range
:
0
~
20mA
(
Remark: By extend
card
)
Multi-fun
ction
input
terminal
DI1
Multi-function
input terminal 1
Programmable
multi-function switch
output terminals is referred
to introduction about input
terminal function(Switch
input and output) on
Chapter 6 terminals
function parameters
(Common port:COM )
(
Detail refer to
DI2
Multi-function
input terminal 2
DI3
Multi-function
input terminal 3
DI4
Multi-function
input terminal 4
24