GT200 series general purpose inverter instruction manual
Featured Parameter
(BIT)
Value
Significance
BIT5
~
BIT4
00B
Modify step length to 1
Others
Reserved
BIT7
~
BIT6
01B
Able to be modified.
10B
Unable to be modified during running
11B
Factory set, and users cannot modify.
00B
Actual parameter, unable to be modified.
BIT11
~
BIT8
0000B
No unit
0001B
Unit is HZ
0010B
Unit is A
0011B
Unit is V
0100B
Unit is r/min
0101B
Unit is linear speed (m/s)
0110B
Unit is percentage (%)
Others
Reserved
BIT12
1
Modify the upper limit according to 4-bit
byte restriction.
0
Modify the upper limit according to
character restriction.
BIT15
~
BIT13
Reserved
The inverter control parameters could complete inverter start, stop, and set running
frequency etc., via retrieving the inverter’s state parameters, it could obtain the inverter’s
running frequency, output current, output torque etc. Specific inverter’s control parameters
and state parameters are listed in the following:
Inverter’s Control Parameter Index
Register
Address
Parameter Name
Whether Save after Power off
0x3200
Control command
Character
No
0x3201
Main setting
Main setting value is the running
frequency given.
0x3202
Running frequency
setting
Yes
0x3203
Digit closed-loop given
Yes
0x3204
Pulse closed-loop given
Yes
0x3205
Analog output A01
setting
No
0x3206
Analog output AO2
setting
No
0x3207
Digit output DO setting
No
95