Figure 1
-
Overall Dimensions
Figure 2
Under specific test conditions this heater has been
shown to deliver heat at rates ranging from
9,527
to
18,761
Btu/hr.
THIS APPLIANCE NEEDS PERIODIC INSPECTION AND
REPAIR FOR PROPER OPERATION. CONSULT
OWNER’S MANUAL FOR FURTHER INFORMATION. IT
IS AGAINST FEDERAL REGULATIONS TO OPERATE
THIS APPLIANCE IN A MANNER INCONSISTENT WITH
OPERATING INSTRUCTIONS IN THE OWNER’S
MANUAL.
This wood heater has a manufacturer-set minimum low
burn rate that must not be altered. It is against federal
regulations to alter this setting or otherwise operate this
wood heater in a manner inconsistent with operating
instructions in this manual. U.S. ENVIRONMENTAL
PROTECTION AGENCY Certified to comply with 2020
particulate emission standards using pellet fuel. It is
recommended that smoke and carbon monoxide detectors
be installed in the area where the heater is to be installed.
OUTSIDE COMBUSTION AIR IS MANDATORY IN
MOBILE OR MODULAR HOME INSTALLATIONS.
CAUTION: DO NOT CONNECT TO ANY AIR
DISTRIBUTION DUCT OR SYSTEM.
VENTING AND INSTALLATION
CLEARANCES
CONTACT LOCAL BUILDING OFFICIALS ABOUT RE-
STRICTIONS AND INSTALLATION INSPECTION
REQUIREMENTS IN YOUR AREA.
A LISTED, 4" MINIMUM TYPE "L" PELLET VENT PIPE
IS MANDATORY ON ALL INSTALLATIONS.
DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST
VENTING SYSTEM OF THIS UNIT, DO NOT CONNECT
THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER
APPLIANCE.
Use only listed 3" minimum Type "L" pellet vent and
components for installation. The exhaust vent system must
be attached to the unit and to each adjoining section. All
joints for connector pipe shall be fastened with at least three
screws. If vented horizontally, joints shall be made gas-tight
by sealing with high temperature silicon or material specified
by vent pipe manufacturer. Failure to use listed pellet vent
pipe or install it per manufacturers instructions will void your
warranty.
INSTALL VENT AT CLEARANCES SPECIFIED BY THE
VENT MANUFACTURER
Vent Pipes’ inner and outer diameters may vary. Check with
vent pipe manufacturer for further details.
WARNING: Installation of a Mobile Home Attachment Kit
P/N 10412 and outside combustion air is mandatory in
mobile or modular home installations
although it may
also be used in all residential applications.
An outside air inlet MUST be provided for combustion
and ventilation air.
The air inlet must remain unrestricted
while unit is in use. Outside air connection is located in the
rear of the heater (
Figure 2
). Use conduit pipe or metal flex
pipe and/or fittings to make the air intake hook-up.
CAUTION: STRUCTURAL INTEGRITY OF THE MOBILE
HOME FLOOR, WALLS AND CEILING/ROOF MUST BE
MAINTAINED.
1.
When deciding on the location of your heater and vent
pipe, try to minimize the alteration and reframing of
structural components of the building.
Vent pipe must
be installed so that access is provided for
inspection and cleaning
.
2.
Avoid installing heater in high traffic areas. Keep
children well away from the heater when in operation.
3. A 3" clearance to combustibles must be maintained
for horizontal and vertical venting. When passing
through ceilings or walls, you must use a listed wall
thimble, making sure all combustible materials and
insulation products are a minimum of 3" away from the
pellet vent pipe.
PELLET HEATERS REQUIRE A MINIMUM 5' VERTICAL
RISE FOR PROPER OPERATION. ADDITIONAL RISE
OF 2' FOR EVERY 1' HORIZONTAL BEYOND 1 ½'.
MINIMUM DRAFT REQUIRED IS -.01 IN.WC. @
CONNECTION
.
LOW DRAFT CONDITIONS RESULT IN OVERFEEDING
AND POOR COMBUSTION.
2