10
●If one UPS of parallel system is malfunctioning, first of all, turn off the malfunctioning UPS, then cut off the
input power to the faulty UPS and disconnect the output of faulty UPS to the parallel system, make sure that
there is no electrical connection with malfunctioning UPS, after all of those, it’s safe to do operation.
3.4 External battery connection procedure for long back up type
●For different UPS type, users are instructed to configure different battery voltage as below sheet. More or
less units are forbidden, or else something abnormal or faulty will appear.
Type
Battery Quantity
(unit)
Battery Voltage
(volt)
6KVA
16/20
192V/240V
10KVA
16/20
192V/240V
15KVA
16/20
192V/240V
20KVA
16/20
192V/240V
Note: there are two battery pack options for UPS, 16 units and 20 units. Users can choose the different
battery pack voltage in accordance with different requirements. The default units of batteries to UPS is 16,
and users can not connect 16 batteries to UPS if the UPS should be connected 20 units. Please strictly follow
the procedure of batteries connection, or will get electric shocks.
1. Set the battery switch at ‘OFF’ position, then install batteries in series.
2. Connecting the cables to batteries firstly, or you may get electric shocks if you connect the cables to UPS
firstly. You’d better connect the red cable to battery positive pole ‘+’, black to negative pole ‘-’, so that it would
be much easier to distinguish.
3. Select proper cables to connect the batteries and UPS is very important, and there should be a switch
connected between the battery pack and UPS.
4. Finally, without any load, set on the battery switch which is connected between the UPS and the battery
pack, so that UPS can get connected to batteries, then switch in the mains power, after doing all of those, the
batteries will be charged by the UPS automatically.
BAT
+
-
BAT
+
-
BAT
+
-
BAT
+
-
Positive
Negative
16/20PCS
To UPS terminal blocks
Battery
Breaker
3.5 Network functions
3.5.1 Communication port
Users could monitor the UPS system through the communication port such as standard RS232 port and