28
MODEL
EA906II
EA9010II
EA9015II
EA9020II
Capacity
6KVA/5.4KW
10KVA/9KW
15KVA/13.5KW
20KVA/18KW
INPUT
Rated Voltage
3/1: 360V/365V/380V/400V/415VAC;
1/1: 208V/210V/220V/230V/240VAC.
(Set up by LCD display)
Voltage Range
3/1: Half load (190-520)±5VAC, Full load (277-520)±5VAC;
1/1: Half load (110-300)±5VAC, Full load (160-300)±5VAC.
Frequency
40-70Hz±0.5% (Auto sensing)
Power Factor
3/1: ≥0.95;
1/1: ≥0.99.
BYPASS
Voltage Range
160V-Rated output 32V
Frequency
50/60Hz±5Hz
OUTPUT
Voltage
208V/210V/220V/230V/240Vac Setting available via LCD
Voltage Regulation
±1%
Frequency
Synchronized with utility on AC mode; 50/60±0.1Hz on battery mode
Waveform
Pure sine wave
Crest Factor
3:1
Harmonic Distortion
≤2%(Linear load); ≤5%(Non-linear load)
Transfer Time
AC mode to battery mode: 0ms
Inverter mode to bypass mode: 0ms
Overload Capability
105%-125%: Transfer to bypass after 3mins;
125%-150%: Transfer to bypass after 30s;
>150%: Transfer to bypass after 100ms
EFFICIENCY
AC Mode
≥93%
Battery Mode
≥92%
ECO Mode
≥98%
BATTERY
DC Voltage
192V/240VDC
Inbuilt Battery of Standard
Model
16*7AH
16*9AH
NO
Charge
Current
Standard Model
1A
Long Time Model
7A
Typical Recharge Time
8 hours recover to 90% capacity
ALARM
Utility Failure
Beep/4s
Battery Low
Beep/1s
Overload
Beep Twice/1s
UPS Fault
Long Beep
ENVIRONMENT
Humidity
20~90% RH @ 0~40
℃(non
-condensing)
Noise Level
≤58dB (1m)
≤60dB (1m)