16 Technical data
24
ESR5-NO-41-24VAC-DC
12/19 MN049009EN
www.eaton.com
Mechanical service life
10
7
cycles
Switching capacity (360 cycles/h)
4 A (24 V DC)
4 A (230 V AC)
Switching capacity (3600 cycles/h)
2.5 A (24 V (DC-13))
3 A (230 V (AC-15))
Output fuse
10 A gL/gG NEOZED (N/O contact)
6 A gL/gG NEOZED (N/C contact)
General data
Relay type
Electromechanical relay with forcibly guided contacts
in accordance with EN 50205
Nominal operating mode
100 % operating factor
Degree of protection
IP20
Min. degree of protection of inst. location
IP54
Mounting position
any
Mounting type
DIN rail mounting
Type of housing
PBT yellow/black
Air and creepage distances between the power circuits
according to DIN EN 50178/VDE 0160
Rated insulation voltage
250 V
Rated surge voltage / insulation
Basic insulation 4 kV:
between all current paths and housing
Safe isolation, reinforced insulation 6 kV:
between A1/A2 and 13/14, 23/24, 33/34, 43/44
between S11/S12/S33/S34 and 13/14, 23/24, 33/34,
43/44
between 51/52 and 13/14, 23/24, 33/34, 43/44
Pollution degree
2
Surge voltage category
III
Dimensions
W x H x D
22.5 x 99 x 114.5 mm
Connection data
Conductor cross section, solid
0.2 mm
2
- 2.5 mm
2
Conductor cross section, stranded
0.2 mm
2
- 2.5 mm
2
Conductor cross section AWG/kcmil
24
- 12
Stripping length
7 mm
Screw thread
M3
Ambient conditions
Ambient temperature (operation)
-20 °C - 65 °C (observe derating)
Ambient temperature (storage/transport)
-40 °C - 70 °C
Max. permissible relative humidity (operation)
75 % (on average, 85% infrequently, non-condensing)
Max. permissible humidity (storage/transport)
75 % (on average, 85% infrequently, non-condensing)
Maximum altitude
≦
2000 m (above sea levelNN)
Shock
15 g
Vibration (operation)
10 Hz - 150 Hz, 2 g