8 Technical data
ESR5-BWS-31-24VAC-DC
12/19 MN049005EN
www.eaton.com
17
Safety parameters for IEC 61508 - Low demand
1)
SIL
3
MTTF
d
17913 years
PFD
avg
1.50 x 10
-4
Proof test interval
75 months
Safety characteristic data according to EN ISO 13849
1)
Category
4
Performance Level
e
CCF
Passed
1) Valid up to 8760 cycles per year