IB131006EN
Page 50
Effective 07/2017
Figure 6-10 Attaching Closure
Test Tool at HP
Step 5 -
Mount the transparent CloSure
TM
Test Tool with
two bolts and washers. Refer to Figures
6-19, 6-20
and
Table
6.4
for appropriate mounting holes. Hand tighten
the bolts (Figures
6-9, 6-10, 6-19
and
6-20
)
.
Step 6 -
A Sanford
®
Sharpie
®
black fine point permanent
marker, item no. 30001, is recommended for this next
step. Place the marker tip in the proper hole (
“C”
)
.
Refer
to Figure
6-19
and make a heavy mark on the tape as
shown in Figure
6-10.
Figure 6-11 Manually Charging Closing Springs
Step 7 -
Charge the closing springs with the
maintenance tool. Continue charging the closing springs
until a “click” is heard and the status indicator shows
“Charged”
(Figure
6-11
)
.
Step 8 -
While holding the marker tip on the tape, close
the breaker (Figure
6-12
)
.
Step 9 -
Move the marker back and forth horizontally
approximately 15
in both directions to create a line on
Figure 6-12 Manually Closing Circuit Breaker with
Marker in Hole “C”.
Figure 6-13 Top View of Cam and Marker interface
Figure 6-14 Move Marker 15
o
to Right
the tape that identifies the closed rest position (Figures
6-13, 6-19
and
6-15
)
.
Summary of Contents for 120VCP-W25
Page 28: ...IB131006EN Page 22 Effective 07 2017 position Courtesy of NationalSwitchgear com ...
Page 44: ...IB131006EN Page 38 Effective 07 2017 Figure 5 5A CONTINUED Courtesy of NationalSwitchgear com ...
Page 65: ...IB131006EN Page 59 Effective 07 2017 Courtesy of NationalSwitchgear com ...
Page 67: ...IB131006EN Page 61 Effective 07 2017 Courtesy of NationalSwitchgear com ...