Table 6.4 Troubleshooting Guide (continued from previous page)
Symptom
Probable Cause
Corrective Actions
Circuit breaker cannot be closed
locally, but can be closed remotely
Controller or pushbutton switch
wiring problem
Inspect for loose wires into con-
troller or open pushbutton switch
Circuit breaker makes no attempt to
close with either local (manual) or
remote controls
Circuit breaker interlock is
preventing close
Make sure circuit breaker is fully
racked in or out on enclosure
(drawout only)
Verify that emergency open
handle is in a vertical position
Check all interlock switches for
obstructions
Controller wiring problem
Inspect for loose wires into con-
troller
Damaged auxiliary switch or close
coil
Contact EATON Service Center