I.B. 8295A61H03
Page 42
Effective 7/97
SYMPTOM
INSPECTION AREA
PROBABLE DEFECTS
Fails To Close
• Closing Spring charged but
• No Closing Sound
• Control Power
breaker does not close
(Close Coil does not pick up)
(Fuse blown or
switch off)
• Secondary
Disconnects
• Anti-Pump Relay
(Y relay N. C. contact
open or burned or relay
picks up)
• Close Coil
(Open or burned)
• Latch Check Switch
(Contact open-bad
switch or trip bar
not reset)
• Auxiliary Switch
(b contact open or
burned)
• Motor Cut-off
(Contacts open or
burned)
• Trip Coil Assembly
(Clapper fails to reset)
• Pole Shaft
(Not open fully)
• Trip Latch Reset Spring
(Damaged or Missing)
• Closing Sound
• Trip Bar-D Shaft
but no close
(Fails to remain reset)
• Trip Latch-Hatchet
(Fails to remain reset)
• Trip Floor Tripper
(Fails to remain reset)
• Close Latch
(Binding)
• Close Latch Roller
(Binding)
• Trip Circuit Energized
Undesirably Closes
• Control Circuit
• Close Circuit
(CS/C Getting Shorted)
• Close Release Latch
(Fails to reset)
• Mechanism
• Close Floor Tripper
(Fails to reset)
Summary of Contents for 150 VCP-WR 1500