39
Instruction Book
IB182017EN February 2017 www.eaton.com
5kV, 7.5kV, & 15kV DHP-VR
Replacement Circuit Breaker
Sttp 5 -
Clean the far left cam with a mild solvent such as alcohol.
Place the tape around the cam starting from the bottom up. Make
certain that the tape adheres well to the cam surface. (Figure 6.6).
Sttp 6 -
Mount the transparent CloSure™ Test Tool (Figure 6.7b)
with two bolts and washers. Refer to Figure 6.7a and Table 6.1 for
approximate mounting holes. Hand tighten the bolts.
Sttp 7 -
Using a red Sanford
®
Sharpie
®
fine point permanent marker
(or equivalent), place the marker tip in the proper hole (“C”)
located over the cam and make a heavy mark on the tape by
moving the marker as described in Figures 6.9, 6.11, and 6.12.
Remove the marker from the hole.
Sttp 8 -
Charge the closing springs with the maintenance tool
(Charging handle). Continue charging the closing springs until
a “click” is heard and the status indicator shows “CHARGED”
(Figure 6.8).
Sttp 9 -
Place the marker back in the hole. While holding the marker
tip against the tape, close the breaker (Figure 6.10). Remove the
marker from the hole.
Sttp 10 -
While closely observing the pole shaft at the right side of
the circuit breaker (Figure 6.11), recharge the closing springs with
the maintenance tool. As the circuit breaker is recharged, there
should be no movement of the pole shaft. If there is movement of
the pole shaft while recharging, this indicates a problem with the
circuit breker - stop the test and consult the factory.
Sttp 11 -
Open the circuit breaker, then close it, then reopen it.
Verify that the mark made in Step 7 is aligned with the pen
opening. If it is not aligned, this indicates a problem with the
circuit breaker - stop the test and consult the factory.
Sttp 12 -
Inspect the circuit breaker to assure it is in the open
position and the closing springs are discharged. Alternately
depress the Open and Close clappers a few times to ensure the
circuit breaker is completely discharged. Remove the transparent
CloSure™ Tool.
Sttp 13 -
Remove the tape from the cam and place it on a sheet of
paper that can be kept as a record of the test. Record the date of
the test, person conducting the test, circuit breaker serial number,
and the operations counter on the tape or paper (Figures 6.14 and
6.15).
Sttp 14 -
Evaluate the CloSure™ performance by comparing the
test tape with the illustration in Figure 6.16. Measure the over
travel “X”. If “X” is greater than or equal to 0.6”, the circuit breaker
performance is satisfactory. If “X” is less than 0.6”, this indicates
a problem with the circuit breaker - consult the Power Breaker
Center for technical support.
Sttp 15 -
Reassemble the front cover onto the circuit breaker.
Return the circuit breaker to its original configuration and setup.
Figurt 6.7. Attaching CloSurt™ Ttst Tool at Holt “A” & “B”
Figurt 6.7.b. Front Vitw of CloSurt™ Tool Showing Mounting /
Ttsting Holt Locations (6352C49H01)
A-1
A-2
A-3
A-4
B-1
B-2
C-2
C-3
C-4 C-5
C-6
C-1
Tablt 6.1. CloSurt™ Tool Mounting / Ttsting Locations by
Circuit Brtaktr Typt
ELEMENT
DESIGNATION
APPROXIMATE
MECHANISM
CHASSIS WIDTH
(INCH)
UPPER
MOUNTING
HOLE
LOWER
MOUNTING
HOLE
MARKER
PLACEMENT
HOLE
18WR
20WR
29WR
18
20
27
A1
A1
A1
B2
B2
B2
C1
C2
C5
Figurt 6.7.c. Typical Circuit Brtaktr Front Vitw with CloSurt™
Tool Attachtd (Approximatt Mtchanism Chassis Width)
Width