1. Description
1.7 Conditions for Underwriters Laboratories Inc. (UL) listing
1.7 Conditions for Underwriters Laboratories Inc. (UL) listing
1.7.1 Panel-PC
The following conditions must be met in order for the certification of UL 61010-2-201
as per Panel-PC to apply:
Do not exceed a mounting position range between 45° towards the back and 10°
towards the front for landscape and vertical installation
Operation up to an altitude of 2000 m (above sea level)
Overvoltage category II
Pollution Degree 2
Suitable power supply for class III (SELV in conformity with UL 61010-2-201)
Permissible voltage range -25%/+50% of rated operating voltage 24 V
DC
.
USB power restricted to a maximum total connected load of 9 W
Type rating
Use in type 4X or type 12 enclosures, use indoors only, at dry locations only
IP65 not evaluated by UL
Ambient temperature 0°C to 45°C
Maximum relative humidity of 95% for temperatures of up to 45 °C, derated linearly
to a relative humidity of 50% at 40 °C.
The torque used to tighten the screw terminals on the plug-in connection for the sup-
ply voltage must not exceed 0.5 - 0.6 Nm (4.4 -5.3 lb-in).
1.7.2 Terminal
The following conditions must be met in order for the certification of UL 61010-2-201
as per Terminal to apply:
Do not exceed a mounting position range between 45° towards the back and 10°
towards the front for landscape and vertical installation
Operation up to an altitude of 2000 m (above sea level)
Overvoltage category II
Pollution Degree 2
Suitable power supply for class III (SELV in conformity with UL 61010-2-201)
Permissible voltage range -15%/+20% of rated operating voltage 24 V
DC
Type rating
Use in type 4X or type 12 enclosures, use indoors only, at dry locations only
IPxx not evaluated by UL
Ambient temperature 0°C to 45°C
24
XP-504
04/2022 MN048028EN Eaton.com
Summary of Contents for 199996
Page 1: ...Manual 04 2022 MN048028EN XP 504 Manual...
Page 4: ......
Page 86: ...5 Commissioning 5 2 Running the XP 504 86 XP 504 04 2022 MN048028EN Eaton com...
Page 98: ...7 Operating System 7 2 Windows 10 Enterprise LTSC 98 XP 504 04 2022 MN048028EN Eaton com...
Page 100: ...8 Faults 100 XP 504 04 2022 MN048028EN Eaton com...
Page 130: ...Appendix A 2 Further usage information 130 XP 504 04 2022 MN048028EN Eaton com...